8. TRENDLOG.EXE PROGRAM
The “Maximum Value” box is the upper limit set point for this 
trend log source data. The default value is 10000.
The “Minimum Value” box is the lower limit set point for this trend 
log source data. The default value is 0.
The
 
button cancels this operation and returns you to the
previous screen.
All of the options on the left side of the Logic Address Dialog Box 
require that a valid “Satellite address Number” be entered in the 
box provided for proper operation.
The options on the middle and right side of the Logic Address 
Dialog Box are WCC3 system points that do not require a “Satellite 
Address Number” or “Point Number” for proper operation. These 
options must have a “Global Index” number entered in the box 
provided for proper operation.
Valid WCC3 point numbers
Satellite Address number – 1 to 239
Binary Input – 1 to 8 (Sat analog input used as Binary Input)
Analog Input – 1 to 8
Analog Output – 1 to 8
Control Output Heat – 1 to 8
Control Output Cool – 1 to 8 
Data Register A – 1 to 8
Data Register B – 1 to 8
Runtime – 1 to 8
Logic Switch – 1 to 16
Binary Outputs – 1 to 16
Global Analog – 1 to 256
Global Binary – 1 to 512
Week Schedule – 1 to 128
Optimal Start – 1 to 128
Global Light – 1 to 500
Global Heat – 1 to 500
Global Cool – 1 to 500
After selecting the WCC3 system point that you wish to trend log, 
you now must click 
to fi nish your selection of the WCC3
system point you wish to trend log.
The
button cancels this operation and returns you to the
previous screen.
The save trend log data to ODBC data base check box.
Open Database Connectivity (ODBC) provides a standard software 
API method for using database management systems. The Data 
format is normally saved in data format that only the WattMaster 
trend log program can retrieve. But there is an option to save the 
data in an “ODBC” type of format so that Microsoft Access / SQL 
type programs can access, retrieve, and manipulate the data that 
is saved from the fi les that the WCCTrendlog.exe program can 
create. 
After selecting the “Save trend log data to ODBC database” check 
box, you will need to enter a logically named ODBC database 
source name and an ODBC database table name so that later you 
can retrieve the data from this ODBC named database fi le.
Running the Program