4. SCUSCR.EXE SCREENS
WCC III Technical Guide
4-37
Satellite: Unit:
The satellite fi eld is used to input a valid SAT 3d address
number. The unit number is used to select a valid TUC
(Terminal Unit Controller) that is connected to the SAT 3d
controller.
Valid SAT 3d addresses are in groups of 4, starting at address
4. You can not start a SAT 3d address with a 5, 6, 7, 9, 10, 11,
13, 14, 15 etc. It must be a derivative of address 4, example 4,
8, 12, 16, 20, 24, 28, etc. If there is a question with Satellite
addressing, please check the Satellite summary screen to see if
a valid SAT 3d exists before continuing.
Figure 4-10: Single Duct Cooling Only - Pressure Independent Status Screen
Single Duct Cooling Only Pressure Independent Status Screen
Each SAT 3d uses up the address space of the equivalent
of 4 regular SAT III controllers. See Table 4-4: “SAT 3d
Addressing to TUC control points” for a further explanation.
Certain TUC control points have been shoehorned into SAT 3d
control points so that they may be used in global calculations.
Location
The location fi eld is a user-programmable fi eld name that is
used to identify the location of the WCC3 VAVBOX zone or
space that the WCC3 VAVBOX II is controlling. (There is
space in this fi eld for 20 alphanumeric characters.)
Single Duct Cooling-Only Screens –
Pressure Independent
This is the main summary screen for the WCC3 VAV BOX
II software for the WCC III system, and there should be
suffi cient information on this screen that by simply viewing of
this screen an operator can detect if the VAV BOX II controller
is operating correctly or not.