Setup global map view screen – WattMaster WM-WCC3-TGD-01B User Manual
Page 761

WCC III Technical Guide
20-3
20. GLOBAL BRIDGE BOARD INSTALLATION
SET GLOBAL MAP VIEW
From the WCCUtility.EXE program there are two choices for the 
“WCC II to WCC III Global Bridge” board. The fi rst selection 
choice is 
. This is where global information
can be sent from the WCC II system to the WCC III - MCD.
Get Global Value From Satellite:
Enter the address for the
“WCC II to WCC III Global Bridge” board. This value should be 
higher than the last satellite number on your system. After entering 
the address, press the 
button to lock in
the address.
NOTE:
The “WCCII to WCCIII Global Bridge” will
not show on the Satellite Summary Screen.
Set Update Speed: xxxx Milli-second:
1000 milliseconds is
entered for each “WCC II to WCC III Global Bridge” board on 
the system. If you have three “WCC II to WCC III Global Bridge” 
boards, then a value of 3000 milliseconds needs to be entered for 
each “WCC II to WCC III Global Bridge” board. When desired 
value is entered, press the 
button to lock in
the “Set Update Speed” value.
Enter the number of the global
analog you wish to send from the WCCII to the WCCIII and press 
the button. The global will be added to the Global Analog fi eld at 
the bottom of the screen. There is no limitation to the number of 
global analogs entered.
Enter the number of the global analog
you wish to delete from the Global Analog box and press the 
button. The global analog will disappear from the list.
Enter the number of the global binary
you wish to send from the WCCII to the WCCIII and press the 
button. The global will be added to the Global Binary fi eld at the 
bottom of the screen. There is no limitation to the number of global 
binaries entered.
Enter the number of the global binary
you wish to delete from the Global Binary box and press the button. 
The global binary will disappear from the list.
NOTE:
To receive global analog and global binary values on
the WCC III system from the WCC II system, the mode for the 
analog global and binary global on the WCC III system must 
be set to external. See Section 3 for programming globals.
Setup Global Map View Screen
Figure 20-2: Set Global Map View Window