WCC III Technical Guide
3-45
WCC3.EXE SCREEN DESCRIPTIONS
Sensor Type
This is a choice fi eld for Analog types only. A list of available
choices will be displayed at the bottom of the screen:
Resistor+, RawCount, Thermistor+> You may make your selection by pressing the until the desired Analog Type has been selected and then pressing . Thermistor+ is to be used if you are using a thermistor type sensor NOTE: The associated analog input jumper on the satellite controller must also be set to “THERM” in order for this screen to display the proper temperature value. Pattern for Values Associated With This Input: Specifi es where you would like the decimal point to appear in the < x,xxx , xxx.x , xx.xx , x.xxx > You may make your selection by pressing the until the desired data pattern has been selected and then pressing . Degree Type: Specifi es how you would like the temperature displayed, in < ºF, ºC > You may make your selection by pressing the until the desired data pattern has been selected and then pressing . Analog Input Thermistor+ Screen Offset: There is an option to change the calibration of a thermistor sensor Units of Measure Message #: 1 A number is entered here that references a message on the On/Off Filter Time Constant: ____ Seconds Specifi es the sampling rate of the analog input. This is used by the < 0, 1, 2, 4, 8, 16, 32, 64 > You may make your selection by pressing the until the desired fi lter time constant has been selected and then pressing . ------ALARMS------ Controlled by: Specifi es the binary value that selects the ON or OFF alarm limits. Alarm Type: Specifi es the priority (or “importance”) level for any alarms Alarm Message # Low: ___ High: ___ Specifi es a pair of message numbers, one for LOW alarms and
that WattMaster Controls has not provided. Other thermistor type
sensors can be connected to the Satellite controller’s analog inputs
with this screen. Please consult the WattMaster Controls factory
for all other thermistor type sensors that you wish to connect to the
Satellite Controller. WattMaster Controls can provide the correct
b0, b1, b3 values at our option.
value displayed by the system. Because this is a “choice” fi eld,
a list of available choices will be displayed at the bottom of the
screen:
Fahrenheit or Celsius. Because this is a “choice” fi eld, a list of
available choices will be displayed at the bottom of the screen:
(Usually due to the position or location of the thermistor sensor)
a few degrees plus or minus from the actual temperature that the
thermistor sensor is actually reading. Acceptable values in this
fi eld are numerical with both positive and negative (+/-) values.
Units Messages Screen. For example, if units-of-measure message
#1 is “Deg F,” entering “1” will cause “Deg F” to be displayed as
the units-of-measure for the analog input.
satellites to “fi lter” (or smooth) the analog input signal. This can be
used on inputs that “jump around” to reduce sporadic load control.
Because this is a “choice” fi eld, the list of available choices will be
displayed at the bottom of the screen:
When this value is OFF, the OFF alarm limits are selected; when it
is ON, the ON alarm limits are selected.
generated by this input. Alarm types range from one (highest
priority) to eight (lowest priority). The system displays and e-mails
higher priority alarms fi rst. (The fi rst fi ve alarm priorities (1-5)
have e-mail-out-on-alarm capabilities.)
the second for any HIGH alarms. These numbers are used by
the system to reference a message which is entered on the Alarm
Message Screen.