WCC3.EXE SCREEN DESCRIPTIONS
Mode: 10 Lead-Lag 
Specifi es the mode used to generate the ON or OFF value of the 
binary global. Because this is a choice fi eld, the following list of 
available choices will be displayed at the bottom of the screen:
Alarm-by-Class, One Shot, Clock, Delay, PWM,  Lead-Lag> Make your selection by pressing the   once for each  choice until the desired mode has been selected, and then press  . Whenever you change modes, you must fi rst clear the  existing screen by using the   feature. Lead-Lag Mode is a dual or two-stage control scheme to balance  Operation based on:  This fi eld must have a valid WCC III binary structured value that  NOTE:  The very next Global Binary is the 2nd global binary  value for the lag (Secondary) and must be set to Global Binary  “Mode 3: External” for proper operation.  Proof of fl ow:  This fi eld must have a valid WCC III binary input value and is  Binary Global Lead Lag Mode Screen  BINARY GLOBAL SCREEN LEAD LAG MODE Binary Global Screen’s WCC III Logical Address is GBXXX, where GB = Global Binary and XXX = Global Binary Address
the operating run time between two units for redundant operation. 
Each time the current source (the binary point that this global’s 
operation is based on) is turned “ON”, this program will determine 
which unit to turn on, either Lead or Lag, based on the current 
Lead-Lag ratio and the current Lead-Lag run times.
must be used as a binary input value for this screen to operate 
correctly. Satellite Binary Input (XXXLWW), Satellite Control 
“C” output (XXXkYc), Satellite Control “H” output (XXXkYh)), 
Satellite Binary Output (XXXOWW), Global Binary (GBZZZ), 
where WW equals 1 to 16, XXX equals 1 to 239, Y equals 1 to 8, 
and ZZZ equals 1 to 512. 
used as a feedback mechanism to ensure that the valve/pump has 
actually turned on and is working properly. 