4. SCUSCR.EXE SCREENS
WCC III Technical Guide
4-25
VAV BOX CONTROLLER
Satellite: _ 4
Unit:
1
Location:
Version: 3.04
[ GLOBAL BINARIES ]
Unit operates in Occupied Mode when............:
W1 is active.
Force Damper Fully Open when GB(x).............:
GB1 is active.
Force Damper Fully Closed when GB(x)...........:
GB10 is active.
Force Damper to Maximum when GB(x).............:
GB11 is active.
Force Damper to Minimum when GB(x).............:
GB12 is active.
Force Damper to Fixed Damper/Airflow when GB(x):
//// is active.
Force Damper to Re-Calibrate when GB(x)........:
GB13 is active.
[ GLOBAL ANALOGS ]
Duct Temperature is read on GA (x).............:
////
EMS Setpoint Spread Precentage is read on GA(x):
////
Main Fan Status to read on GA(x)...............:
GA12
[ CALIBRATION ]
Space Temp Sensor Calibration Offset...........:
0.0°F
Discharge Sensor Calibration Offset............:
0.0°F
< Ctrl-Right Arrow > for Next Page
Screen File: SCR220.SDF
< Ctrl-Left
Arrow > for Previous Page
Figure 4-4: VAV BOX Globals Screen
VAV BOX III Globals Screen
VAV BOX Globals Screen
The VAV BOX Globals Screen is used to set up the occupied/
unoccupied conditions for the control of the zone and forced 
overrides of the damper for special “set” conditions. The calibration 
offsets for the zone’s space and discharge temperature sensors can 
also be set on this screen.
Unit operates in Occupied Mode when…………....:
This ON/OFF value is used to set week schedule/optimal start for 
the occupied or unoccupied status of the VAV BOX III zone. Valid 
Inputs for this fi eld are: 0, 1, GB1 to GB512, W1 to W128, S1 to 
S128.
Force Damper Fully Open when GB(x) …………..:
The VAVBOX TUC-2R controller damper can be globally forced 
to one of several positions with the use of Global Binaries. There 
may be times at which the end user will want to have maximum 
airfl ow in the conditioned zoned space. Such forced overrides 
could include Global binary determinations for morning warmup, 
troubleshooting, air balancing, CO2 reduction, pre-cooling or pre-
heating for a meeting room, smoke detection (Remember that the 
WCC III is not rated for fi re life safety) etc. On a Global force 
mode it will be possible to force multiple VAVZONE boxes open or 
closed with a single global command. (Ignores Airfl ow Reading.)
Force Damper Fully Closed when GB(x) ………....:
The VAVBOX TUC-2R controller damper can be globally forced 
to one of several positions with the use of Global Binaries. There 
may be times at which the end user will want to have minimum 
airfl ow in the conditioned zoned space. Such forced overrides 
could include Global binary determinations for troubleshooting, 
air balancing, night set back, smoke detection (Remember that the 
WCC III is not rated for fi re life safety) etc. On a Global force 
mode it will be possible to force multiple VAVZONE boxes open or 
closed with a single global command. (Ignores Airfl ow Reading.)
Force Damper to Maximum when GB(x) ………....:
The VAVBOX TUC-2R controller damper can be globally forced 
to one of several positions with the use of Global Binaries. There 
may be times at which the end user will want to have maximum 
airfl ow in the conditioned zoned space. Such forced overrides 
could include Global binary determinations for morning warmup, 
troubleshooting, air balancing, CO2 reduction, pre-cooling or 
preheating for a meeting room, smoke detection (Remember that 
the WCC III is not rated for fi re life safety) etc. On a Global force 
mode it will be possible to force multiple VAVZONE boxes open or 
closed with a single global command. (Ignores Airfl ow Reading.)