Sat iii controller, Wcc3.exe screen descriptions, Logic switch screen – WattMaster WM-WCC3-TGD-01B User Manual

Page 194: Wcc iii technical guide 3-80, Sat iii

background image

WCC3.EXE SCREEN DESCRIPTIONS

WCC III Technical Guide

3-80

SAT III CONTROLLER

8

7

SAT ADDRESS

2

1

4

8

A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

WattMaster Controls Inc.

BINARY
INPUTS

BINARY
INPUTS

L8

ON OFF

128

32

16

64

L4

L3

L2

L1

L6

L5

L7

L11

L12

ON OFF

L10

L9

ON OFF

L15

L16

L14

L13

C

H

4

3

5
6

2

1

LOCAL SET

STATUS 2

STATUS 3

STATUS 1

HSS XMIT

LOCAL SET

LOCAL SET DISABLE

BATT ON/ OFF

PULSE INPUT

OPTION 1

TEST

OPTION 3

OPTION 2

ON OFF

STATUS

HSS REC

SAT XMIT

SAT REC

ANALOG INPUT

JUMPER SELECTION

A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.

CURRENT
INPUT

THERMISTOR
INPUT

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

0 TO 10V
INPUT

0 TO 5V
INPUT

0 TO 1V
INPUT

0 - 10V

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

PROGRAMMABLE CONTROLLER

SAT III

WCC3 BINARY IN W/ TIME DELAY

WATTMASTER CONTROLS, INC

YS102072 REV 2

24VAC

120VAC

TO OTHER
SAT III OR TO
WCC III - MCD

CONNECTION FROM A SAT III CONTROLLER TO WCC3 BINARY INPUT W/TIME DELAY BOARD USING THE "NEW" HSS CABLE CONNECTION METHOD

HSS CABLE - ORDER STANDARD LENGTHS OF 1 FOOT, 1.5 FOOT, 3 FEET, 25 FEET, 40 FEET, 80 FEET AND 120 FEET MAX

24

V

A

C

GND

TO OTHER
SAT III OR TO
WCC III - MCD
WIRE "T" TO "T"
"R" TO "R"
"SHD" TO "SHD"

UP TO TWO WCC3 BINARY INPUT W/TIME
DELAY BOARDS MAY BE WIRED TO THE

SAT III CONTROLLER USING THIS

METHOD. CONNECT THE FIRST WCC3
BINARY INPUT W/TIME DELAY BOARD
HSS PORT TO THE SAT III CONTROLLER
HSS COMMUNICATIONS PORT AND
THEN CONNECT THE FIRST WCC3
BINARY INPUT W/TIME DELAY BOARD
TO THE SECOND WCC3 BINARY INPUT
W/TIME DELAY BOARD VIA THE SECOND
HSS PORT ON THE FIRST WCC3 BINARY
INPUT W/TIME DELAY BOARD .
ADDITIONALLY, UP TO TWO V-OUT RELAY
BOARDS MAY ALSO BE CONNECTED

SAT III

TO THE

CONTROLLER HSS PORT.

BINARY INPUT BOARD GETS POWER AND COMMUNICATIONS TO AND FROM THE SAT III FROM THIS HSS CABLE

WARNING:

OBSERVE POLARITY

BETWEEN THE SAT III AND THE
BINARY INPUT BOARD - GROUND
CONNECTIONS MUST BE THE SAME.

SAT III
HSS PORT

DRY INPUT CONTACTS ONLY
CONTACT CLOSURE TO GROUND
ONLY. NO 24VAC INPUTS

SEE MANUAL FOR

DIP SWITCH SETTINGS

120VAC WIRING IS BY OTHERS

THE VA RATING FOR THE SAT III CONTROLLER IS 15VA.
THE VA RATING FOR THE WCC3 BINARY INPUT BOARD (OE431-01) IS 5 VA.
THE VA RATING FOR THE WCC3 V-OUT RELAY BOARD (OE430-01) IS 10 VA.
THE VA RATING FOR THE WCC3 V-OUT RELAY BOARD (OE430-02) IS 20 VA.

Logic Switch Screen