Sat iii controller, Sat iii, Sat 2 type" v-out board – WattMaster WM-WCC3-TGD-01B User Manual
Page 720
16. WCC III V-OUT RELAY BOARD INSTALLATION
WCC III Technical Guide
16-2
8
7
SAT ADDRESS
2
1
4
8
A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4
L3
L2
L1
L6
L5
L7
L11
L12
ON OFF
L10
L9
ON OFF
L15
L16
L14
L13
C
H
4
3
5
6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SET
LOCAL SET DISABLE
BATT ON/ OFF
PULSE INPUT
OPTION 1
TEST
OPTION 3
OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.
CURRENT
INPUT
THERMISTOR
INPUT
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
0 - 10V
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
2
1
3 4
2
1
3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX
0-15VDC
OUTPUT
MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY
TO HSS EXPANSION BOARDS.
UP TO TWO WCC3 BINARY INPUT W/TIME DELAY
BOARDS, AND UP TO THREE V-OUT RELAY BOARDS
MAY BE CONNECTED TO A SAT III CONTROLLER
HSS COMMUNICATIONS PORT.
SAT III CONTROLLER
24VAC
24VA
C
GND
GROUND
WARNING:
OBSERVE POLARITY
BETWEEN THE SAT III AND THE WCC3
V-OUT RELAY BOARD - GROUND
CONNECTIONS MUST BE THE SAME.
USING THIS METHOD CAN NOT
DAMAGE EITHER DEVICES.
TO OTHER
SAT III OR TO
WCC III - MCD
24VAC
120VAC
TO OTHER
SAT III OR TO
WCC III - MCD
WIRE "T" TO "T"
"R" TO "R"
"SHD" TO "SHD"
8
7
SAT ADDRESS
2
1
4
8
A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4
L3
L2
L1
L6
L5
L7
L11
L12
ON OFF
L10
L9
ON OFF
L15
L16
L14
L13
C
H
4
3
5
6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SET
LOCAL SET DISABLE
BATT ON/ OFF
PULSE INPUT
OPTION 1
TEST
OPTION 3
OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.
CURRENT
INPUT
THERMISTOR
INPUT
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
0 - 10V
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
2
1
3 4
2
1
3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX
0-15VDC
OUTPUT
MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY
24VAC
24VA
C
GND
GROUND
SAT III CONTROLLER
TO OTHER
SAT III OR TO
WCC III - MCD
WIRE "T" TO "T"
"R" TO "R"
"SHD" TO "SHD"
TO OTHER
SAT III OR TO
WCC III - MCD
24VAC
120VAC
"SAT 2 TYPE" V-OUT BOARD
A CHIPSWITCH MUST BE
PRESENT FOR EACH OUTPUT
TO FUNCTION
DAISY CHAIN OUT TO
OTHER WCC3 V-OUT RELAY
BOARD OR TO OTHER WCC3
BINARY INPUT W/TIME
DELAY BOARDS THAT ARE
TO BE CONNECTED TO THE
SAT III HSS
COMMUNICATIONS PORT.
CONNECTION FROM A SAT III CONTROLLER TO WCC3 V-OUT RELAY BOARD USING THE "NEW" HSS CABLE CONNECTION METHOD
CONNECTIONS # 1 THRU # 8 TO THE OLD SAT II TYPE V-OUT BOARD INPUTS VIN 1 THRU VIN 8 CONNECTION METHOD.
WARNING:
OBSERVE POLARITY
BETWEEN THE SAT III AND THE "OLD"
SAT II TYPE V-OUT BOARD.
THE GROUND CONNECTIONS MUST BE
THE SAME. DAMAGE TO THE SAT III
CONTROLLER OR TO THE "OLD" SAT II
TYPE V-OUT BOARD CAN RESULT IN
VOIDING WARRANTY.
DUPLICATING THE ORIGINAL SAT II
V-OUT TYPE CONNECTION.
CONNECT ALL EIGHT OF THE SAT III
ANALOG OUTPUTS V-OUT #1 THRU
V-OUT # 8 TO THE "OLD" SAT II TYPE
V-OUT BOARD INPUTS # 1 THRU # 8.
CONNECT ONE OF THE SAT III GND
CONNECTIONS TO THE "OLD" SAT II
TYPE V-OUT BOARD GND
CONNECTION IF POSSIBLE.
TO HSS EXPANSION BOARDS.
UP TO TWO WCC3 BINARY INPUT W/TIME DELAY
BOARDS, AND UP TO THREE V-OUT RELAY BOARDS
MAY BE CONNECTED TO A SAT III CONTROLLER
HSS COMMUNICATIONS PORT.
SAT III CONTROLLER CONNECTION FOR A
BINARY OUTPUT TYPE CONNECTION.
WCC3 V-OUT RELAY
N.O. ONLY CONTACTS
(OE430-01)
120VAC WIRING IS BY OTHERS
THE VA RATING FOR THE SAT III CONTROLLER IS 15VA.
THE VA RATING FOR THE WCC3 BINARY INPUT BOARD IS 5 VA.
THE VA RATING FOR THE WCC3 V-OUT RELAY N.O. BOARD IS 10 VA.(OE430-01)
120VAC WIRING IS BY OTHERS
THE VA RATING FOR THE SAT III CONTROLLER IS 15VA.
THE VA RATING FOR THE WCC2 V-OUT RELAY BOARD IS 10 VA.
THE VA RATING FOR THE WCC3 V-OUT RELAY N.O. BOARD IS 10 VA.(OE430-01)
THE VA RATING FOR THE WCC3 V-OUT RELAY N.O./N.C. BOARD IS 20 VA. (OE430-02)
CONNECTION FROM A SAT III CONTROLLER TO AN OLD SAT II TYPE V-OUT BOARD USING THE “OLD” HARD WIRED WAY. WIRING THE SAT III CONTROLLER’S V-OUT
OE430-01 Installation