Scuscr.exe screens, Wcc iii vav box iii operation modes – WattMaster WM-WCC3-TGD-01B User Manual
Page 322

WCC III Technical Guide
4-12
4. SCUSCR.EXE SCREENS
In all cases, before the series box fan can be activated, the air 
damper is driven fully closed and held that way for 30 seconds to 
make sure the series box fan hasn’t inadvertently started to spin 
backwards. Once the series box fan starts, it waits an additional 
10 seconds to allow the fan to spin up before it starts to open the 
damper and introduce airfl ow from the HVAC unit fan.
NOTE:
If check for main fan status is selected, the series fan
will activate any time the HVAC unit fan is operating.
Parallel Flow Fan Terminals
In the Unoccupied Cooling mode the parallel fan will be off 
whether check for main fan status has been selected or not. If 
check for mainfan status has been selected, the damper will be 
held at the Nite/Reheat minimum until the space temperature 
begins to rise to 0.5 ºF below the unoccupied cooling setpoint. If 
check for main fan status has not been selected, the damper will 
be held in the fully closed position until the space temperature 
begins to rise to 0.5 ºF below the unoccupied the cooling 
setpoint.
Space Heating Mode
During unoccupied mode, the HVAC unit is normally off. 
Unoccupied Space Heating mode is initiated by the temperature in 
the space falling below the Unoccupied Space Heating Setpoint.
If the VAVBOX TUC-2R controller is in the Unoccupied Supply 
Air Cooling mode because one or more of the VAVBOX TUC-2R 
controllers has a cooling demand and another VAVBOX controller 
has a heating demand, the damper/airfl ow for the VAVBOX 
controller requiring heating will position itself to provide the Night/
Reheat setpoint amount of air into the space. No modulation open 
will occur because the space does not want the cold air currently 
being supplied by the air handler.
When the VAVBOX TUC-2R controller is in the Unoccupied 
Supply Air Heating mode, the damper will be held at the Night/
Reheat minimum position until the space temperature begins to fall 
below the Unoccupied heating setpoint. As the space temperature 
falls to 0.5 ºF above the unoccupied Heating Setpoint, the damper/
airfl ow calculation causes the air valve to open proportionally until 
the maximum setpoint is achieved at 1.5 ºF below the setpoint. 
This is a 2 ºF proportional window starting 0.5 ºF above the heating 
setpoint to 1.5 ºF below the heating setpoint.
As with the Occupied Mode of operation, two different 
confi gurations are available for the Unoccupied Space Heating 
mode. If the box is confi gured to allow reheat during HVAC Heat 
mode, the reheat relays can be activated even when the VAVBOX 
TUC-2R controller is in the Supply Air Heating mode. If the 
box is confi gured not to allow reheat when the HVAC unit is in 
Heat mode, the box heat relays will be de-energized when the 
VAVBOX TUC-2R controller is in Supply Air Heating mode. In 
either confi guration, when the VAVBOX TUC-2R controller is 
in the Supply Air Heating mode, the damper will modulate open 
proportionally to the space demand. The proportional window for 
the space temperature is 0.5 ºF above to 1.5 ºF below the heating 
setpoint. This allows the space to take advantage of the warm 
supply air in the duct.
If check for main fan status is not selected and the VAVBOX 
terminal unit has auxiliary heat (baseboard heat etc.) that does not 
require the HVAC unit fan to operate, reheat can be used without the 
HVAC unit fan operating. If check for main fan status is selected, 
the reheat will only operate when the HVAC unit fan is operating.
The VAVBOX TUC-2R controller can activate auxiliary heating 
relays if the relay Expansion Board has been connected and the 
correct number of heating stages (1,2, or 3) has been confi gured. 
During demands for heat, the fi rst stage will activate whenever the 
space temperature drops below the heating setpoint. The second 
stage will activate if the space temperature falls 1.0 ºF below 
the heating setpoint. The third stage will activate if the space 
temperature falls 2.0 ºF below the heating setpoint. There is a two-
minute delay between staging. This prevents stages from activating 
at the same time. Once a heating stage has been activated, it must 
remain on for at least one minute. Once it has been deactivated, it 
must remain off for at least two minutes. The third stage relay will 
deactivate when the space temperature rises to within 1.0 ºF of the 
heating setpoint. The second stage relay will deactivate when the 
space temperature rises to the heating setpoint. The fi rst stage relay 
will deactivate when the space temperature rises above the heating 
setpoint by 1.0 ºF. 
See Table 4-3: Relay Staging - Unoccupied Mode for a complete 
layout of the various fan & heat relay staging points.
Modulating (Proportional) Heat
The VAVBOX TUC-2R controller expansion board also provides 
an analog output for control of a modulating hot water valve or 
SCR electric heater. It provides a 0-10 VDC signal to control the 
heating device. When the space temperature drops to 0.5 ºF above 
the Heating Setpoint the output starts at 0 VDC and ramps up to 10 
VDC at 1.5 ºF below the Heating Setpoint.
WCC III VAV BOX III Operation Modes