WCC3.EXE SCREEN DESCRIPTIONS
V
OUT
GND
+V
ATI
1 TO 8
1 TO 8
NONE
LOAD
RESISTOR
2 WIRE THERMISTOR TYPE - Thermistor Scaling Factor
FLUSHMOUNT SENSOR (WM PART # OE210)
ANALOG INPUT SCALING - From Sat Analog Input Screen
Description:
Type: Thermistor
Pattern for values associated with this input: xxx.x
Degree Type: F Units of measure message#: 1
Filter time constant: 0 Seconds
Input Jumper must be set to THERM
There are berg jumpers that are under the SAT III cover that must be set.
JOX corresponds to X = 1 to 8 for the Analog Input jumper.
Example:
JO1 is for Analog Input #1
JO8 is for Analog Input #8
An Input Load Resistor must not be used. Internally, the SAT III
controller calculates the resistance of the thermistor back to a Voltage so
that the SAT III controller can calculate the proper temperature. RX
corresponds to X = 1 to 8 for the Analog Input load resistor. Example as
follows:
R1 is for Analog Input #1 (NO RESISTOR SHOULD BE INSTALLED)
R8 is for Analog Input #8 (NO RESISTOR SHOULD BE INSTALLED)
Testing with an Ohmmeter:
Disconnected from the SAT III controller, measure from TMP to GND
on the sensor. You should get an ohm meter measurement that
corresponds to the Temperature. 10,000 ohms equals 77.0 DegF
Y
S
101724
RE
V.
0
P1
RV1
C1
S1
SHLD
RV2
R
TB2
T
GND
AUX
OUT
R1
TM
TB1
Identify the Sensor
Circuit Board YS#
YS101724
JOX
THERM
0-10V
0-5V
0-1V
CONNECTIONS ON
SAT III CONTROLLER
10K OHM
TYPE 3
THERMISTOR
Analog Input Screen