Single duct cooling only screen – WattMaster WM-WCC3-TGD-01B User Manual
Page 340

WCC III Technical Guide
4-30
4. SCUSCR.EXE SCREENS
Single Duct Cooling-Only Screens
This is the main summary screen for the WCC3 VAV BOX II 
software for the WCC III system, and there should be suffi cient 
information on this screen that by simply viewing of this screen 
an operator can detect if the VAV BOX II controller is operating 
correctly or not.
Figure 4-6: Single Duct Cooling Only - Pressure Dependent Status Screen
Single Duct Cooling Only Screen
Satellite: Unit:
The satellite fi eld is used to input a valid SAT 3d address number. 
The unit number is used to select a valid TUC (Terminal Unit 
Controller) that is connected to the SAT 3d controller.
Valid SAT 3d addresses are in groups of 4, starting at address 4. 
You can not start a SAT 3d address with a 5, 6, 7, 9, 10, 11, 13, 
14, 15 etc. It must be a derivative of address 4, example 4, 8, 12, 
16, 20, 24, 28, etc. If there is a question with Satellite addressing, 
please check the Satellite summary screen to see if a valid SAT 3d 
exists before continuing.
Each SAT 3d uses up the address space of the equivalent of 4 
regular SAT III controllers. See Table 4-4: “SAT 3d Addressing 
to TUC control points” for a further explanation. Certain TUC 
control points have been shoehorned into SAT 3d control points so 
that they may be used in global calculations.
Location
The location fi eld is a user-programmable fi eld name that is used 
to identify the location of the WCC3 VAVBOX zone or space that 
the WCC3 VAVBOX II is controlling. (There is space in this fi eld 
for 20 alphanumeric characters.)
Space Temperature
This is the current temperature of the zoned area that the WCC3 
VAVBOX II is controlling. It is listed in degrees Fahrenheit. 
(Zone temperatures sensors WM Part# OE210, OE211, OE212, 
or OE213) A duct sensor in the return air ducting may also be used 
for return air control of the VAVBOX zone (WM Part# OE230, or 
OE231)