WCC3.EXE SCREEN DESCRIPTIONS
WCC III Technical Guide
3-172
Binary Global Alarm-By-Class Mode Screen
In Local Set this global defaults to _____.
Specifi es the state (or value) of the binary global when the satellite 
is in the Local Set mode. The satellite is in local set when it has lost 
communications with the front end computer.
Since the fi rst fi eld is a “choice” fi eld, the list of available choices 
will be displayed at the bottom of the screen:
Make your selection by pressing the
once for each
choice until the desired contact state has been selected, and then 
press 
.
------------ALARM-------------
Set Condition: None Type: 0
Message 0
The system has the capability of generating an alarm if the value of 
this binary global is either ON or OFF. 
Set the condition to “None” to not generate an alarm whenever the 
Binary Global is Off or On. Set the condition to “On” to generate 
an alarm whenever this Binary Global is On. Set condition to “Off” 
to generate an alarm whenever this Binary Global is Off.
Because this is a choice fi eld, the list of available choices will be 
displayed at the bottom of the page.
Make your selection by pressing the
once for each
choice until the desired event type has been selected, and then 
press 
.
Type specifi es the priority (or “importance”) level for any alarms 
generated by this input. Alarm types range from one (highest 
priority) to eight (lowest priority). The system displays and e-mails 
higher priority alarms fi rst. (The fi rst fi ve alarm priorities (1-5) 
have e-mail-out-on-alarm capabilities.)
The message number corresponds to a message on the ON/OFF 
Message Screen.