Wcc3.exe screen descriptions, Special purpose keys, Wcc iii technical guide 3-8 – WattMaster WM-WCC3-TGD-01B User Manual
Page 122

WCC3.EXE SCREEN DESCRIPTIONS
WCC III Technical Guide
3-8
Special Purpose Keys
The special purpose keys are a very powerful and necessary part of 
the WCC III system, but they can also be very dangerous if you are 
not sure how to use them. Therefore, most of the special purpose 
keys require that the operator have a Level 3 passcode.
Acknowledge Alarms
—Used at the Analog
Input Summary Screen, Trend Log Run Time Screen, Alarm 
Summary Screen, and Global Analog/Binary Summary Screen.
Display Graphs
—Used at the Analog Trend
Screen, Proportional Reset Screen, and the Look-up Table 
Screen to plot data.
Clear Communication Errors
—Used at
Satellite Summary Screen for troubleshooting, clears 
communication errors on a single satellite.
Manually Reset (Clear) Data
—Used at the
Trend Log Screen, Global Analog Integral Mode to reset 
accumulated consumption, Energy Consumption Screen to 
reset consumption.
< Ctrl>
Clear Input Data from Present Screen
(clear structure)—Cursor must be in the Home position on the 
screen.
—Used on Custom Screens and
Bitmap Screens to “freeze/unfreeze” the data being displayed.
—Used on Custom Screens
and Bitmap Screens to fi nd the exact location where a point 
was placed on the screen.
—Used on Custom
Screens and Bitmap Screens to delete the location where a 
point was placed on the screen.
When an alarm occurs within the system, the alarm condition 
appears on its respective summary screen as a fl ashing display 
generally on the right side of the screen. Once the alarm has been 
acknowledged, one of two possible conditions will be displayed.
The fi rst condition is when an alarm is acknowledged, but the 
alarm remains outside of the alarm limits. When this happens, the 
alarm information is still displayed on the screen, but it appears 
solid instead of blinking. The second condition is when an alarm 
is acknowledged AND the alarm is inside the alarm limits. In 
this case, all alarm information for that point is cleared from the 
screen.
To acknowledge new (blinking) alarms, position the cursor (>) 
at the point for which you wish to acknowledge alarms. Once 
positioned, press and hold 
, then press
, and then release
both keys at the same time.
 
The WCC III system has graphs for the Analog Trend Screen, the 
Proportional Reset Screen, and the Look-Up Table Screen that can 
be displayed on the screen and can be printed on the printer using 
the 
,
command.
The graph for the Analog Trend - Trend Logging Screen is accessed 
while the cursor is at the Home position of an Analog Trend Screen. 
Press 
. Press the
key to return to the Analog
Trend Screen.
The Proportional Reset Screen also has a graph that can be 
accessed by pressing 
while the cursor is anywhere on
the Proportional Reset Screen. Press the
key to return to
the Proportional Reset Screen.
To access the graph for the Look-Up Tables (GA 121-128), while 
the cursor is at any position on a Global Analog Look-Up Table, 
press 
to display the Look-Up Table graph. Press the
key to return to the Global Analog Look-Up Table.
Special Purpose Keys