WCC3.EXE SCREEN DESCRIPTIONS

WCC III Technical Guide

3-8

Special Purpose Keys

The special purpose keys are a very powerful and necessary part of
the WCC III system, but they can also be very dangerous if you are
not sure how to use them. Therefore, most of the special purpose
keys require that the operator have a Level 3 passcode.

:

Acknowledge Alarms

—Used at the Analog

Input Summary Screen, Trend Log Run Time Screen, Alarm
Summary Screen
, and Global Analog/Binary Summary Screen.

:

Display Graphs

—Used at the Analog Trend

Screen, Proportional Reset Screen, and the Look-up Table
Screen
to plot data.

:

Clear Communication Errors

—Used at

Satellite Summary Screen for troubleshooting, clears
communication errors on a single satellite.

:

Manually Reset (Clear) Data

—Used at the

Trend Log Screen, Global Analog Integral Mode to reset
accumulated consumption, Energy Consumption Screen to
reset consumption.

< Ctrl>:

Clear Input Data from Present Screen

(clear structure)—Cursor must be in the Home position on the
screen.

Toggle Updating

—Used on Custom Screens and

Bitmap Screens to “freeze/unfreeze” the data being displayed.

Find Logic Address

—Used on Custom Screens

and Bitmap Screens to fi nd the exact location where a point
was placed on the screen.

Delete Logic Address

—Used on Custom

Screens and Bitmap Screens to delete the location where a
point was placed on the screen.

: Acknowledge Alarms

When an alarm occurs within the system, the alarm condition
appears on its respective summary screen as a fl ashing display
generally on the right side of the screen. Once the alarm has been
acknowledged, one of two possible conditions will be displayed.

The fi rst condition is when an alarm is acknowledged, but the
alarm remains outside of the alarm limits. When this happens, the
alarm information is still displayed on the screen, but it appears
solid instead of blinking. The second condition is when an alarm
is acknowledged AND the alarm is inside the alarm limits. In
this case, all alarm information for that point is cleared from the
screen.

To acknowledge new (blinking) alarms, position the cursor (>)
at the point for which you wish to acknowledge alarms. Once
positioned, press and hold

, then press

, and then release

both keys at the same time.

: Display Graphs

The WCC III system has graphs for the Analog Trend Screen, the
Proportional Reset Screen, and the Look-Up Table Screen that can
be displayed on the screen and can be printed on the printer using
the

,

command.

The graph for the Analog Trend - Trend Logging Screen is accessed
while the cursor is at the Home position of an Analog Trend Screen.
Press

. Press the

key to return to the Analog

Trend Screen.

The Proportional Reset Screen also has a graph that can be
accessed by pressing

while the cursor is anywhere on

the Proportional Reset Screen. Press the

key to return to

the Proportional Reset Screen.

To access the graph for the Look-Up Tables (GA 121-128), while
the cursor is at any position on a Global Analog Look-Up Table,
press

to display the Look-Up Table graph. Press the

key to return to the Global Analog Look-Up Table.

Special Purpose Keys