Wcc3.exe screen descriptions, Analog global screen – WattMaster WM-WCC3-TGD-01B User Manual
Page 242

WCC3.EXE SCREEN DESCRIPTIONS
WCC III Technical Guide
3-128
The term local set means that communication is lost between 
the MCD and the satellite controllers. If the MCD stops 
communicating, the global analog values will be gone. This 
input allows you to specify a default value for the global 
analog if the MCD quits communicating. You may input a fi xed 
number, or you may choose to select LAST VALUE. If LAST 
VALUE is chosen, the global analog will default to the value it 
had when communications with the MCD were lost.
Mode
Because this is a “choice” fi eld, the list of available choices will 
be displayed at the bottom of the screen:
External, Dual Valve, Proportion, Dual Ramp,  Multi-Proportion, Pulse Start> Make your selection by pressing the   once for each  choice until the desired mode type has been selected, and then press  . One of the following screens will appear, depending on  which choice you select:   Averaged List    Math Function   Sorted List      Look-Up Table  Integral        External     Sliding Window  Dual Valve   Average      Proportion   Accumulation    Dual  Ramp           Multi-Proportion           Pulse  Start CAUTION:  Select the mode before entering any other data on  an Analog Global Screen. If other information is entered before  the mode is selected, there is a chance that the global analog  will not perform properly. If data has already been entered and  you want to change the mode, you must fi rst clear the screen by  using the   feature, and then exit to the Global  Analog Summary Screen before re-entering data. Analog Global Screen