Function library, Limit value setting, Stop – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 93

background image

Function library

Limit value setting

7−22

L

EDB82MV752 EN 5.2

Adjustment

Relation between output frequency and synchronous speed of the motor:

n

rsyn

+ C0011 @ 60

p

r

rsyn

Synchronous motor speed [min

−1

]

C0011

Max. output frequency [Hz]

p

No. of pole pairs (1, 2, 3, ...)

Example:
4−pole asynchronous motor: p = 2, C0011 = 50 Hz

n

rsyn

+ 50 @ 60

2

+ 1500 min

*1

C0010

"Minimum output frequency" characteristics:

·

C0010 is approached via the acceleration ramp.

·

C0010 has no effect
– on the analog input 2 of the application I/O.

– when the setpoint is selected via frequency input.

·

C0010

³

C0011:

– C0011 is approached via the acceleration ramp regardless of the selected analog setpoint.

– The output frequency is limited to C0011.
– The analog input gain must be set to zero (C0027 = 0), to ensure a trouble−free operation.

C0011

"Maximum output frequency" characteristics:

·

When selecting fixed setpoint (JOG) C0011 acts as limitation.

·

C0011 is an internal normalisation variable! Bigger changes should only be made when the
controller is inhibited!

(

Stop!

Set C0011 so that the maximum permissible motor speed will not be exceeded.

Otherwise the motor can be destroyed.

C0239

"Lower frequency limitation" characteristics:

·

When using standard I/O, C0239 is approached without acceleration ramp (jolt!). When using
application I/O, C0236 can be used to set an acceleration time for C0239.

·

C0239 = 0.00 Hz only allows one direction of rotation.

Tip

·

For output frequencies > 300 Hz, switching frequencies < 8 kHz must be avoided.

·

The display values of C0010 and C0011 can be related to a process variable under C0500
and C0501.