4 dc braking (dcb), Dc braking (dcb), Function library – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 101: Acceleration, deceleration, braking, stopping
![background image](/manuals/566255/101/background.png)
Function library
Acceleration, deceleration, braking, stopping
7−30
L
EDB82MV752 EN 5.2
7.5.4
DC braking (DCB)
Description
The DC−injection brake enables quick deceleration of the drive to standstill without using an external
brake resistor. The DC−injection brake can be activated via terminal or automatically.
·
The braking torque amounts to approx. 20 ... 30 % of the rated motor torque. It is lower than
for braking in generator mode with external brake resistor.
·
A brake voltage or a brake current can be selected.
·
Automatic DC braking improves the starting performance of the motor e.g. when operating
hoists.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0019
Operating threshold
− automatic DC
injection brake
(auto DCB)
0.10
0.00
= inactive
{0.02 Hz}
650.00 Hold time
ð C0106
Deactivate automatic DC injection brake
(auto DBC):
·
at active lower frequency limitation
(C0239)
·
at operating mode C0014 = 5
^ 7−30
C0035*
v
DC injection brake
(DCB) control mode
0
0
Brake voltage selection under C0036
Hold time
ð C0107
^ 7−30
1
Brake current selection under C0036
C0036
Voltage/current DC
injection brake
(DCB)
а
0.00
{0.01 %}
150.00 %
а
Depending on the controller
·
Reference M
r
, I
r
·
Setting applies to all mains voltages
permitted
^ 7−30
C0106
Hold time for
automatic
DC−injection brake
(Auto DCB)
0.50
0.00
= auto DCB not active
{0.01 s}
999.00
=
¥
Hold time, if DC−injection brake is activated
because the value falls below the setting
under C0019.
^ 7−30
C0107
Hold time DC
injection brake
(DCB)
999.00 1.00
{0.01 s}
999.00
=
¥
Hold time, if DC−injection brakes are
activated via an external terminal or control
word.
^ 7−30
C0196*
v
Activation of
auto–DCB
0
0
Auto−DCB active, if PCTRL1−SET3 < C0019
^ 7−30
1
Auto−DCB active, if PCTRL1−SET3 < C0019 and
NSET1−RFG1−IN < C0019
Adjustment
1. Use C0035 to select whether a brake voltage or a brake current shall be selected.
2. Enter the brake voltage or brake current under C0036 in percent.
– If C0035 = 0, the data refers to the rated voltage of the controller.
– If C0035 = 1, the data refers to the rated current of the controller.
3. Select how to activate the DC injection brake:
– Via digital input signal (configuration with C0410/15)
– Automatically when the values are fallen below the operating threshold C0019 (condition:
C0106 > 0.00 s)
Activate DC−injection braking via input signal (DCB)
Link C0410/15 with a digital signal source.
In case of HIGH−active inputs, the DC−injection braking (DCB) remains active as long as the signal
is on HIGH level.
After the hold time (C0107) has elapsed, the controller sets pulse inhibit (keypad display:
c).
)
Note!
In addition to the free configuration in C0410 you can also use the fixed assignment
in C0007 to link the function with a digital input.