background image

Function library

Acceleration, deceleration, braking, stopping

7−30

L

EDB82MV752 EN 5.2

7.5.4

DC braking (DCB)

Description

The DC−injection brake enables quick deceleration of the drive to standstill without using an external
brake resistor. The DC−injection brake can be activated via terminal or automatically.

·

The braking torque amounts to approx. 20 ... 30 % of the rated motor torque. It is lower than
for braking in generator mode with external brake resistor.

·

A brake voltage or a brake current can be selected.

·

Automatic DC braking improves the starting performance of the motor e.g. when operating
hoists.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0019

Operating threshold
− automatic DC
injection brake
(auto DCB)

0.10

0.00
= inactive

{0.02 Hz}

650.00 Hold time

ð C0106

Deactivate automatic DC injection brake
(auto DBC):

·

at active lower frequency limitation
(C0239)

·

at operating mode C0014 = 5

^ 7−30

C0035*

v

DC injection brake
(DCB) control mode

0

0

Brake voltage selection under C0036

Hold time

ð C0107

^ 7−30

1

Brake current selection under C0036

C0036

Voltage/current DC
injection brake
(DCB)

а

0.00

{0.01 %}

150.00 %

а

Depending on the controller

·

Reference M

r

, I

r

·

Setting applies to all mains voltages
permitted

^ 7−30

C0106

Hold time for
automatic
DC−injection brake
(Auto DCB)

0.50

0.00
= auto DCB not active

{0.01 s}

999.00

=

¥

Hold time, if DC−injection brake is activated
because the value falls below the setting
under C0019.

^ 7−30

C0107

Hold time DC
injection brake
(DCB)

999.00 1.00

{0.01 s}

999.00

=

¥

Hold time, if DC−injection brakes are
activated via an external terminal or control
word.

^ 7−30

C0196*

v

Activation of
auto–DCB

0

0

Auto−DCB active, if PCTRL1−SET3 < C0019

^ 7−30

1

Auto−DCB active, if PCTRL1−SET3 < C0019 and
NSET1−RFG1−IN < C0019

Adjustment

1. Use C0035 to select whether a brake voltage or a brake current shall be selected.

2. Enter the brake voltage or brake current under C0036 in percent.

– If C0035 = 0, the data refers to the rated voltage of the controller.
– If C0035 = 1, the data refers to the rated current of the controller.

3. Select how to activate the DC injection brake:

– Via digital input signal (configuration with C0410/15)
– Automatically when the values are fallen below the operating threshold C0019 (condition:

C0106 > 0.00 s)

Activate DC−injection braking via input signal (DCB)

Link C0410/15 with a digital signal source.

In case of HIGH−active inputs, the DC−injection braking (DCB) remains active as long as the signal
is on HIGH level.

After the hold time (C0107) has elapsed, the controller sets pulse inhibit (keypad display:

c).

)

Note!

In addition to the free configuration in C0410 you can also use the fixed assignment
in C0007 to link the function with a digital input.