3 oscillation damping, Oscillation damping, Function library – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 87
![background image](/manuals/566255/87/background.png)
Function library
Selection of control mode, optimisation of operating behaviour
7−16
L
EDB82MV752 EN 5.2
7.2.3
Oscillation damping
Description
Suppression of idling oscillations when:
·
the rated power of controller and motor of a drive do not match, e.g. at operation with high
switching frequency and the related power derating
·
Operation of higher−pole motors
·
Operation of special motors
Compensation of resonances in the drive
·
Some asynchronous motors can show this behaviour when being operated with an output
frequency of approx. 20 ... 40 Hz. As a result, operation can be instable (current and speed
fluctuations).
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0079
Oscillation damping
2
0
{1}
140
^ 7−16
Adjustment
1. Approach with speed oscillations.
2. Reduce the speed oscillations by changing C0079 step by step. Additional indicators for
smooth running can be:
– uniform motor current
– reduction of mechanical vibrations in the bearing seat
)
Note!
Compensate the resonances in speed−controlled operation via the parameters of
the controller only.