beautypg.com

3 oscillation damping, Oscillation damping, Function library – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 87

background image

Function library

Selection of control mode, optimisation of operating behaviour

7−16

L

EDB82MV752 EN 5.2

7.2.3

Oscillation damping

Description

Suppression of idling oscillations when:

·

the rated power of controller and motor of a drive do not match, e.g. at operation with high
switching frequency and the related power derating

·

Operation of higher−pole motors

·

Operation of special motors

Compensation of resonances in the drive

·

Some asynchronous motors can show this behaviour when being operated with an output
frequency of approx. 20 ... 40 Hz. As a result, operation can be instable (current and speed
fluctuations).

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0079

Oscillation damping

2

0

{1}

140

^ 7−16

Adjustment

1. Approach with speed oscillations.

2. Reduce the speed oscillations by changing C0079 step by step. Additional indicators for

smooth running can be:

– uniform motor current
– reduction of mechanical vibrations in the bearing seat

)

Note!

Compensate the resonances in speed−controlled operation via the parameters of
the controller only.