Function library

Display of operating data, diagnostics

7−87

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0051*

Output frequency
with slip
compensation
(MCTRL1−NOUT
+SLIP) or
act. process
controller value
(PCTRL1−ACT)

−650.00

{0.02 Hz}

650.00

The value set will be lost when
switching the mains!
Operation without process controller
(C0238 = 2):

·

Display only: Output frequency with slip
compensation (MCTRL1−NOUT+SLIP)

Operation with process controller
(C0238 = 0, 1):

·

Selection, if C0412/5 = FIXED−FREE (not
assigned)

·

Display if C0412/5 is linked with a signal
source

^ 7−54

C0052*

Motor voltage
(MCTRL1−VOLT)

0

{V}

1000 Only display

C0053*

DC−bus voltage
(MCTRL1−DCVOLT)

0

{V}

1000 Only display

C0054*

Apparent motor
current
(MCTRL1−IMOT)

0.0

{A}

2000.0 Only display

C0056*

Controller load
(MCTRL1−MOUT)

−255

{%}

255 Only display

Under C0311 you can change the display
value for the operating modes vector
control or sensorless torque control.

C0061*

Heatsink
temperature

0

{

°C}

255 Only display

·

If the heatsink temperature is >

J

max

5 °C:

– The warning

OH

will be sent.

– The chopper frequency will be

reduced to 4 kHz, if C0144 = 1

·

If the heatsink temperature is >

J

max

:

– Controller sets TRIP

OH

C0138*

Process controller
setpoint 1
(PCTRL1−SET1)

0.00

−650.00

{0.02 Hz}

650.00

The value set will be lost when
switching the mains!

·

Selection if C0412/4 = FIXED−FREE

·

Display if C0412/4

¹ FIXED−FREE

^ 7−53

C0189*
(A)

Output signal
compensator
(PCTRL1−FOLL1−OU
T)

−650.00

{0.02 Hz}

650.00 Only display

Compensator = PCTRL1−FOLL1

C0320
(A)

Actual process
controller value
(PCTRL1−ACT)

−650.00

{0.02 Hz}

650.00 Only display

C0321
(A)

Process controller
setpoint
(PCTRL1−SET)

−650.00

{0.02 Hz}

650.00 Only display

C0322
(A)

Process controller
output without
precontrol
(PCTRL1−OUT)

−650.00

{0.02 Hz}

650.00 Only display

C0323
(A)

Ramp function
generator input
(NSET1−RFG1−IN)

−650.00

{0.02 Hz}

650.00 Only display

C0324
(A)

Ramp function
generator output
(NSET1−NOUT)

−650.00

{0.02 Hz}

650.00 Only display

C0325
(A)

PID controller
output
(PCTRL1−PID−OUT)

−650.00

{0.02 Hz}

650.00 Only display

C0326
(A)

Process controller
output
(PCTRL1−NOUT)

−650.00

{0.02 Hz}

650.00 Only display