Appendix

Code table

14−29

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0250*
(A)

Torque threshold 1
(MCTRL1−MSET1)

0.0

−200.0

{0.1 %}

200.0 Related to rated motor torque

C0251*
(A)

Torque threshold 2
(MCTRL1−MSET2)

0.0

−200.0

{0.1 %}

200.0 Related to rated motor torque

Comparison value for setting the digital
output signal MSET2=MACT (torque
threshold 2 = actual torque value)

·

If the difference between
MCTRL1−MSET2 and MCTRL1−MACT is
within C0253:

– MSET2=MACT = HIGH after time set

under C0255

C0252*
(A)

Difference
threshold for
MSET1=MACT

0.0

0.0

{0.1 %}

100.0

C0253*
(A)

Difference
threshold for
MSET2=MACT

0.0

0.0

{0.1 %}

100.0

C0254*
(A)

Delay
MSET1=MACT

0.000

0.000

{0.001 s}

65.000 "Debouncing" of digital output signals

MSET1=MACT

·

Sets MSET1=MACT = HIGH if the
following still applies after time set:

– Difference between MCTRL1−MSET1

and MCTRL1−MACT or C0250 is
within the threshold under C0252

·

Transition HIGH

ð LOW without delay

C0255*
(A)

Delay
MSET2=MACT

0.000

0.000

{0.001 s}

65.000 "Debouncing" of digital output signals

MSET2=MACT

·

Sets MSET2=MACT = HIGH if the
following still applies after time set:

– Difference between MCTRL1−MSET2

and MCTRL1−MACT is within values
set under C0253

·

Transition HIGH

ð LOW without delay

C0265

v

Configuration motor
potentiometer

3

0

Start value = power off

·

Start value: output frequency which is
approached with Tir (C0012) when the
mains is switched on and the motor
potentiometer is activated:

– "Power off" = act. value if mains is

off

– "C0010": Minimum output frequency

from C0010. The setpoint must have
exceeded C0010 before.

– "0" = output frequency 0 Hz

·

C0265 = 3, 4, 5:

– QSP reduces the motor potentiometer

along the QSP ramp (C0105)

^ 7−41

1

Start value = C0010

2

Start value = 0

3

Start value = power off
QSP, if UP/DOWN = LOW

4

Start value = C0010
QSP, if UP/DOWN = LOW

5

Start value = 0
QSP, if UP/DOWN = LOW

C0304

Service codes

Modifications only by Lenze Service!

...

C0309