Appendix
Code table
14−29
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0250*
(A)
Torque threshold 1
(MCTRL1−MSET1)
0.0
−200.0
{0.1 %}
200.0 Related to rated motor torque
C0251*
(A)
Torque threshold 2
(MCTRL1−MSET2)
0.0
−200.0
{0.1 %}
200.0 Related to rated motor torque
Comparison value for setting the digital
output signal MSET2=MACT (torque
threshold 2 = actual torque value)
·
If the difference between
MCTRL1−MSET2 and MCTRL1−MACT is
within C0253:
– MSET2=MACT = HIGH after time set
under C0255
C0252*
(A)
Difference
threshold for
MSET1=MACT
0.0
0.0
{0.1 %}
100.0
C0253*
(A)
Difference
threshold for
MSET2=MACT
0.0
0.0
{0.1 %}
100.0
C0254*
(A)
Delay
MSET1=MACT
0.000
0.000
{0.001 s}
65.000 "Debouncing" of digital output signals
MSET1=MACT
·
Sets MSET1=MACT = HIGH if the
following still applies after time set:
– Difference between MCTRL1−MSET1
and MCTRL1−MACT or C0250 is
within the threshold under C0252
·
Transition HIGH
ð LOW without delay
C0255*
(A)
Delay
MSET2=MACT
0.000
0.000
{0.001 s}
65.000 "Debouncing" of digital output signals
MSET2=MACT
·
Sets MSET2=MACT = HIGH if the
following still applies after time set:
– Difference between MCTRL1−MSET2
and MCTRL1−MACT is within values
set under C0253
·
Transition HIGH
ð LOW without delay
C0265
v
Configuration motor
potentiometer
3
0
Start value = power off
·
Start value: output frequency which is
approached with Tir (C0012) when the
mains is switched on and the motor
potentiometer is activated:
– "Power off" = act. value if mains is
off
– "C0010": Minimum output frequency
from C0010. The setpoint must have
exceeded C0010 before.
– "0" = output frequency 0 Hz
·
C0265 = 3, 4, 5:
– QSP reduces the motor potentiometer
along the QSP ramp (C0105)
^ 7−41
1
Start value = C0010
2
Start value = 0
3
Start value = power off
QSP, if UP/DOWN = LOW
4
Start value = C0010
QSP, if UP/DOWN = LOW
5
Start value = 0
QSP, if UP/DOWN = LOW
C0304
Service codes
Modifications only by Lenze Service!
...