Appendix

Code table

14−34

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0410

v

Free configuration
of digital input
signals

Link between digital signal sources and internal digital
signals

A selection made under C0007 is copied
to the corresponding subcode of C0410.
A change of C0410 sets C0007 = 255!

^ 7−68

1 NSET1−JOG1/3

NSET1−JOG1/3/5/7
(A)

1

Digital input X3/E1

Selection of fixed setpoints
C0410/1 C0410/2
C0410/33
LOW LOW LOW
HIGH LOW LOW
LOW HIGH LOW
... ... ...
HIGH HIGH HIGH

active
C0046
JOG1
JOG2
...
JOG7

2 NSET1−JOG2/3

NSET1−JOG2/3/6/7
(A)

2

Digital input X3/E2

3 DCTRL1−CW/CCW

4

Digital input X3/E4

CW = CW rotation
CCW = CCW rotation

LOW
HIGH

4 DCTRL1−QSP

255

Not assigned (FIXED−FREE)

Quick stop (via terminal LOW active)

5 NSET1−RFG1−STOP

255

Not assigned (FIXED−FREE)

Ramp function generator main setpoint stop

6 NSET1−RFG1−0

255

Not assigned (FIXED−FREE)

Ramp function generator input must be set
to "0" for mains setpoint

7 MPOT1−UP

255

Not assigned (FIXED−FREE)

Motor potentiometer functions

8 MPOT1−DOWN

255

Not assigned (FIXED−FREE)

9 Reserved

255

Not assigned (FIXED−FREE)

Do not change 255!

10 DCTRL1−CINH

255

Not assigned (FIXED−FREE)

Controller inhibit (via terminal LOW active)

11 DCTRL1−TRIP−SET

255

Not assigned (FIXED−FREE)

External error (via terminal LOW active)

12 DCTRL1−TRIP−RESE

T

255

Not assigned (FIXED−FREE)

Error reset

13 DCTRL1−PAR2/4

255

Not assigned (FIXED−FREE)

Parameter set changeover
(only possible if C0988 = 0)
C0410/13 and C0410/14 must have the
same source in every parameter sets
used. Otherwise it is not possible to
change between the parameter sets
(error message CE5 or CE7).

14 DCTRL1−PAR3/4

255

Not assigned (FIXED−FREE)

C0410/13 C0410/14
LOW LOW
HIGH LOW
LOW HIGH
HIGH HIGH

active
PAR1
PAR2
PAR3
PAR4

15 MCTRL1−DCB

3

Digital input X3/E3

DC−injection brake

16
(A)

PCTRL1−RFG2−
LOADI

255

Not assigned (FIXED−FREE)

Actual process controller value
(PCTRL1−ACT) must be connected to
process controller ramp function generator
(PCTRL1−RFG2)

17 DCTRL1−H/Re

255

Not assigned (FIXED−FREE)

Manual/remote changeover

18 PCTRL1−I−OFF

255

Not assigned (FIXED−FREE)

Switch off I−component of the process
controller

19 PCTRL1−OFF

255

Not assigned (FIXED−FREE)

Process controller switch off

20 Reserved

255

Not assigned (FIXED−FREE)

Do not change 255!

21 PCTRL1−STOP

255

Not assigned (FIXED−FREE)

Process controller stop (value "frozen")

22 DCTRL1−CW/QSP

255

Not assigned (FIXED−FREE)

Failsafe change of the direction of rotation

23 DCTRL1−CCW/QSP

255

Not assigned (FIXED−FREE)

24 DFIN1−ON

255

Not assigned (FIXED−FREE)

0 = Frequency input not active
1 = Frequency input active
Frequency input configuration under C0425
and C0426