Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 235
Appendix
Code table
14−34
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0410
v
Free configuration
of digital input
signals
Link between digital signal sources and internal digital
signals
A selection made under C0007 is copied
to the corresponding subcode of C0410.
A change of C0410 sets C0007 = 255!
^ 7−68
1 NSET1−JOG1/3
NSET1−JOG1/3/5/7
(A)
1
Digital input X3/E1
Selection of fixed setpoints
C0410/1 C0410/2
C0410/33
LOW LOW LOW
HIGH LOW LOW
LOW HIGH LOW
... ... ...
HIGH HIGH HIGH
active
C0046
JOG1
JOG2
...
JOG7
2 NSET1−JOG2/3
NSET1−JOG2/3/6/7
(A)
2
Digital input X3/E2
3 DCTRL1−CW/CCW
4
Digital input X3/E4
CW = CW rotation
CCW = CCW rotation
LOW
HIGH
4 DCTRL1−QSP
255
Not assigned (FIXED−FREE)
Quick stop (via terminal LOW active)
5 NSET1−RFG1−STOP
255
Not assigned (FIXED−FREE)
Ramp function generator main setpoint stop
6 NSET1−RFG1−0
255
Not assigned (FIXED−FREE)
Ramp function generator input must be set
to "0" for mains setpoint
7 MPOT1−UP
255
Not assigned (FIXED−FREE)
Motor potentiometer functions
8 MPOT1−DOWN
255
Not assigned (FIXED−FREE)
9 Reserved
255
Not assigned (FIXED−FREE)
Do not change 255!
10 DCTRL1−CINH
255
Not assigned (FIXED−FREE)
Controller inhibit (via terminal LOW active)
11 DCTRL1−TRIP−SET
255
Not assigned (FIXED−FREE)
External error (via terminal LOW active)
12 DCTRL1−TRIP−RESE
T
255
Not assigned (FIXED−FREE)
Error reset
13 DCTRL1−PAR2/4
255
Not assigned (FIXED−FREE)
Parameter set changeover
(only possible if C0988 = 0)
C0410/13 and C0410/14 must have the
same source in every parameter sets
used. Otherwise it is not possible to
change between the parameter sets
(error message CE5 or CE7).
14 DCTRL1−PAR3/4
255
Not assigned (FIXED−FREE)
C0410/13 C0410/14
LOW LOW
HIGH LOW
LOW HIGH
HIGH HIGH
active
PAR1
PAR2
PAR3
PAR4
15 MCTRL1−DCB
3
Digital input X3/E3
DC−injection brake
16
(A)
PCTRL1−RFG2−
LOADI
255
Not assigned (FIXED−FREE)
Actual process controller value
(PCTRL1−ACT) must be connected to
process controller ramp function generator
(PCTRL1−RFG2)
17 DCTRL1−H/Re
255
Not assigned (FIXED−FREE)
Manual/remote changeover
18 PCTRL1−I−OFF
255
Not assigned (FIXED−FREE)
Switch off I−component of the process
controller
19 PCTRL1−OFF
255
Not assigned (FIXED−FREE)
Process controller switch off
20 Reserved
255
Not assigned (FIXED−FREE)
Do not change 255!
21 PCTRL1−STOP
255
Not assigned (FIXED−FREE)
Process controller stop (value "frozen")
22 DCTRL1−CW/QSP
255
Not assigned (FIXED−FREE)
Failsafe change of the direction of rotation
23 DCTRL1−CCW/QSP
255
Not assigned (FIXED−FREE)
24 DFIN1−ON
255
Not assigned (FIXED−FREE)
0 = Frequency input not active
1 = Frequency input active
Frequency input configuration under C0425
and C0426