Troubleshooting and fault elimination

Maloperation of the drive

8−2

L

EDB82MV752 EN 5.2

8.3

Drive performance in case of errors

The controller responds differently to the three possible fault types TRIP, message, and warning:
TRIP (keypad display:

a)

·

Switches the power output U, V, W to high resistance until TRIP is reset.

·

The fault indication is entered into the history buffer as "current fault" in C0161.

·

The drive is coasting (no control)!

·

After TRIP reset

(

^ 8−7)

:

– The drive accelerates to its setpoint along the set ramps.
– The fault indication is moved to C0162 as "last fault" and deleted in C0161.

Messages (keypad display:

c)

·

Switches the power outputs U, V, W to high resistance.

·

Messages are not entered into the history buffer.

·

The drive is coasting without control as long as the message is active!

·

If the message is not active anymore, the drive starts automatically.

Warnings

"Heatsink overtemperature" (keypad:OH e)

·

The drive operates under control!

·

The warning signal goes off if the fault is not active anymore.

"Error in motor phase" (keypad:LP1)

"PTC monitoring" (keypad:OH51)

·

The drive operates under control!

·

The fault indication is entered into the history buffer as "current fault" in C0161.

·

After TRIP reset the fault indication is moved to C0162 as "last fault" and deleted in C0161.