Function library, Free connection of digital signals, message output – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 150
Function library
Free connection of digital signals, message output
7−79
L
EDB82MV752 EN 5.2
Selection under C0415/x
Relays/digital output (not inverted)
32
Digital input X3/E1
Picks up/HIGH, if HIGH level is applied to the
corresponding digital input
33
Digital input X3/E2
34
Digital input X3/E3
35
Digital input X3/E4
36 (A)
Digital input X3/E5
37 (A)
Digital input X3/E6
38
PTC input X2.2/T1, X2.2/T2
Picks up/HIGH, if the potential−free switch is connected
to X2.2/T1, X2.2/T2
40 ... 55
AIF control word (AIF−CTRL) Bit 0 ... Bit 15
Picks up/HIGH, if the corresponding bit is set
60 ... 75
CAN−IN1.W1 or FIF−IN.W1 bit 0 ... bit 15
80 ... 95
CAN−IN1.W2 or FIF−IN.W2 bit 0 ... bit 15
100 ... 115
CAN−IN2.W1 bit 0 ... bit 15
120 ... 135
CAN−IN2.W2 bit 0 ... bit 15
140
Torque threshold 1 reached (MSET1=MOUT)
Picks up/HIGH, if the condition is met
141
Torque threshold 2 reached (MSET2=MOUT)
142
Process controller output limit reached (PCTRL1−LIM)
7.11.3
Free configuration of digital process data output words
Description
·
The digital process data output words can be freely assigned to internal digital signals. With
this you can summarise status information which will be automatically assigned to status word
bits:
– The configuration under C0417 is mapped to the AIF status word 1 (C0150), FIF output word
1 (FIF−OUT.W1) and output word 1 of the CAN object 1 (CAN−OUT1.W1).
– The configuration under C0418 is mapped to the AIF status word 2 (C0151), FIF output word
2 (FIF−OUT.W2) and output word 1 of the CAN object 2 (CAN−OUT2.W1).
·
A signal source can be assigned to several targets.