Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 233

background image

Appendix

Code table

14−32

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0351*

v

System bus baud
rate

0

0

500 kbit/s

·

Only for the E82ZAFCC system bus
function module on the FIF interface.

·

Changes will become effective after the
command "reset node"

During operation with 217x
communication modules the baud rate
must be set under C0125.

1

250 kbits/s

2

125 kbits/s

3

50 kbits/s

4

1000 kbits/s (only E82ZAFCC100 function
module)

5

20 kbits/s

C0352*

v

Configuration of
system bus devices

0

0

slave

·

Only for the E82ZAFCC system bus
function module on the FIF interface.

·

Changes will become effective after the
command "reset node"

1

Master

C0353*

V

Source of system
bus address

0
1

C0350 is the source
C0354 is the source

·

Only for E82ZAFCC system bus function
module on FIF interface.

·

Source of the address for system bus
process data channels

1 CAN1 (Sync)

0

Effective for sync control (C0360 = 1)

2 CAN2

0

3 CAN1 (time)

0

Effective for event or time control (C0360 =
0)

C0354*

v

Selective system
bus address

0

{1}

513

·

Only for the E82ZAFCC system bus
function module on the FIF interface.

·

Individual addressing of system bus
process data objects

1 CAN−IN1 (sync)

129

Effective with sync control (C0360 = 1)

2 CAN−OUT1 (sync)

1

3 CAN−IN2

257

4 CAN−OUT2

258

5 CAN−IN1 (time)

385

Effective with event and time control
(C0360 = 0)

6 CAN−OUT1 (time)

386

C0355*

v

System bus
identifier

0

{1}

2047

·

Only for the E82ZAFCC system bus
function module on the FIF interface.

·

Only display

1 CAN−IN1

Identifier of CAN1 with sync control (C0360
= 1)

2 CAN−OUT1

3 CAN−IN2

4 CAN−OUT2

5 CAN−IN1

Identifier of CAN1 with event or time control
(C0360 = 0)

6 CAN−OUT1

C0356*

v

System bus time
settings

0

{1 ms}

65000 Only for E82ZAFCC system bus function

module on FIF interface.

1 boot up

3000

Required for CAN system without master

2 Cycle time

CAN−OUT2

0

0 = event−controlled process data transfer
> 0 = cyclic process data transfer

3 Cycle time

CAN−OUT1

0

0 and C0360 = 0: event−controlled process
data transfer
> 0 and C0360 = 1: cyclic process data
transfer

4 CAN delay

20

Waiting time until cyclic transmission starts
after boot−up

C0357*

v

System bus
monitoring times

0 = monitoring
inactive

{1 ms}

65000 Only for E82ZAFCC system bus function

module on FIF interface.

1 CAN−IN1 (Sync)

0

active if C0360 = 1
TRIP CE1 in case of communication fault

2 CAN−IN2

0

TRIP CE2 in case of communication fault

3 CAN−IN1 (time)

0

active if C0360 = 0
TRIP CE3 in case of communication fault