Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 233
Appendix
Code table
14−32
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0351*
v
System bus baud
rate
0
0
500 kbit/s
·
Only for the E82ZAFCC system bus
function module on the FIF interface.
·
Changes will become effective after the
command "reset node"
During operation with 217x
communication modules the baud rate
must be set under C0125.
1
250 kbits/s
2
125 kbits/s
3
50 kbits/s
4
1000 kbits/s (only E82ZAFCC100 function
module)
5
20 kbits/s
C0352*
v
Configuration of
system bus devices
0
0
slave
·
Only for the E82ZAFCC system bus
function module on the FIF interface.
·
Changes will become effective after the
command "reset node"
1
Master
C0353*
V
Source of system
bus address
0
1
C0350 is the source
C0354 is the source
·
Only for E82ZAFCC system bus function
module on FIF interface.
·
Source of the address for system bus
process data channels
1 CAN1 (Sync)
0
Effective for sync control (C0360 = 1)
2 CAN2
0
3 CAN1 (time)
0
Effective for event or time control (C0360 =
0)
C0354*
v
Selective system
bus address
0
{1}
513
·
Only for the E82ZAFCC system bus
function module on the FIF interface.
·
Individual addressing of system bus
process data objects
1 CAN−IN1 (sync)
129
Effective with sync control (C0360 = 1)
2 CAN−OUT1 (sync)
1
3 CAN−IN2
257
4 CAN−OUT2
258
5 CAN−IN1 (time)
385
Effective with event and time control
(C0360 = 0)
6 CAN−OUT1 (time)
386
C0355*
v
System bus
identifier
0
{1}
2047
·
Only for the E82ZAFCC system bus
function module on the FIF interface.
·
Only display
1 CAN−IN1
Identifier of CAN1 with sync control (C0360
= 1)
2 CAN−OUT1
3 CAN−IN2
4 CAN−OUT2
5 CAN−IN1
Identifier of CAN1 with event or time control
(C0360 = 0)
6 CAN−OUT1
C0356*
v
System bus time
settings
0
{1 ms}
65000 Only for E82ZAFCC system bus function
module on FIF interface.
1 boot up
3000
Required for CAN system without master
2 Cycle time
CAN−OUT2
0
0 = event−controlled process data transfer
> 0 = cyclic process data transfer
3 Cycle time
CAN−OUT1
0
0 and C0360 = 0: event−controlled process
data transfer
> 0 and C0360 = 1: cyclic process data
transfer
4 CAN delay
20
Waiting time until cyclic transmission starts
after boot−up
C0357*
v
System bus
monitoring times
0 = monitoring
inactive
{1 ms}
65000 Only for E82ZAFCC system bus function
module on FIF interface.
1 CAN−IN1 (Sync)
0
active if C0360 = 1
TRIP CE1 in case of communication fault
2 CAN−IN2
0
TRIP CE2 in case of communication fault
3 CAN−IN1 (time)
0
active if C0360 = 0
TRIP CE3 in case of communication fault