Commissioning

Selection of the correct control mode

5−5

L

EDB82MV752 EN 5.2

Application

Operating mode

Stand−alone drives

C0014

recommended

alternatively

with extremely alternating loads

−4−

−2−

with heavy start conditions

−4−

−2−

with speed control (speed feedback)

−2−

−4−

with high dynamic response (e. g. positioning and infeed drives)

−2−

with torque setpoint

−5−

with torque limitation (power control)

−2−

−4−

three−phase AC reluctance motors

−2−

three−phase sliding rotor motors

−2−

three−phase motors with fixed frequency−voltage characteristic

−2−

Pump and fan drives with square−law load characteristic

−3−

−2− / −4−

Group drives
(several motors connected to controller)

identical motors and identical loads

−2−

different motors and/or changing loads

−2−

C0014 = −2−: linear V/f characteristic control

C0014 = −3−: square−law V/f characteristic control

C0014 = −4−: vector control

C0014 = −5−: sensorless torque control