4 limit value setting, 1 speed range, Limit value setting – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 92: Speed range, Function library

background image

Function library

Limit value setting

7−21

L

EDB82MV752 EN 5.2

7.4

Limit value setting

7.4.1

Speed range

Description

The speed setting range required for the application can be set via the selection of output
frequencies:

·

The minimum output frequency (C0010) corresponds to the speed at 0 % speed setpoint
selection.

·

The maximum output frequency (C0011) corresponds to the speed at 100 % speed setpoint
selection.

·

The lower frequency limitation (C0239) sets the speed. Independently of the setpoint, the
value cannot fall below this speed (e.g. for fans, dancer position control, or dry running
protection for pumps).

0 %

[f]

100 %

C0011

C0010

8200vec526

Fig. 7−5

Relation between setpoint and minimum and maximum output frequency

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0010

uSEr

Minimum output
frequency

0.00

0.00

à

14.5 Hz

{0.02 Hz}

650.00

·

C0010 is not effective with bipolar
setpoint selection (−10 V ... + 10 V)

·

C0010 only defines the analog input 1

·

As of software 3.5: If C0010 > C0011,
the drive does not start running with
controller enable.

à

Speed setting range 1 : 6 for Lenze
geared motors: Setting absolutely
required for operation with Lenze
geared motors.

^ 7−21

C0011

uSEr

Maximum output
frequency

50.00

7.50

à

87 Hz

{0.02 Hz}

650.00

C0239

Lowest frequency
limit

−650.00 −650.00

{0.02 Hz}

650.00

·

The value does not fall below limit
independently of the setpoint.

·

If the minimum frequency limitation is
active, the automatic DC−injection brake
(auto DCB) must be deactivated (C0019
= 0 or C0106 = 0).

^ 7−21

C0236
(A)

Acceleration time −
minimum frequency
limitation

0.00

0.00

{0.02 s}

1300.00 Ref. to C0011

Minimum frequency limitation = C0239

^ 7−21