beautypg.com

Function library, Free connection of digital signals, message output – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 147

background image

Function library

Free connection of digital signals, message output

7−76

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0415

v

(cont.)

Possible digital signals for C0415

^ 7−68

AIF control word (AIF−CTRL)

Permanently assigned bits of AIF−CTRL:
Bit 3: QSP
Bit 7: CINH
Bit 10: TRIP−SET
Bit 11: TRIP−RESET

40

Bit 0

...

...

55

Bit 15

CAN−IN1.W1 or FIF−IN.W1

60

Bit 0

...

...

75

Bit 15

CAN−IN1.W2 or FIF−IN.W2

80

Bit 0

...

...

95

Bit 15

CAN−IN2.W1

100

Bit 0

...

...

115

Bit 15

CAN−IN2.W2

120

Bit 0

...

...

135

Bit 15

Status application I/O

Only active for operation with application
I/O

140

Torque threshold 1 reached (MSET1=MOUT)

141

Torque threshold 2 reached (MSET2=MOUT)

142

Limitation of process controller output reached
(PCTRL1−LIM)

143 ...
172

Reserved

255

Not assigned (FIXED−FREE)

C0416

v

Level inversion −
digital outputs

0

0

Level inversion switched off

By entering the sum of the selected values
you can invert several outputs.

^ 7−73

1

Relay K1

1

or digital switching output K1

2

1: applies to version 151
2: applies to version 152

2

X3/A1

4

X3/A2

Only application I/O

8

Relay K2

Relay output K2 only with
8200 vector 15 ... 90 kW

C0423*
(A)

Delay of digital
outputs

0.000

{0.001 s}

65.000 "Debouncing" of the digital outputs

(from version: application I/O E82ZAFA ...
Vx11)

·

Switches the digital output if the linked
signal is still active after the time set.

·

The digital output is reset without delay

^ 7−73

1 Device version 151:

relay output K1
(RELAY)
Device version 152,
153:
Digital switching
output K1

0.000

2 Digital output X3/A1

(DIGOUT1)

0.000

3 Digital output X3/A2

(DIGOUT2)

0.000

Signal linkage

The digital outputs are linked with the internal digital signals by entering the selection figure of the
internal signal in the corresponding subcode of C0415. C0415 can be different for the parameter
sets.