Parameter setting

With communication module LECOM−A (RS232)

6−13

L

EDB82MV752 EN 5.2

Code

Parameter

Important

No.

Designation

LECOM
format

Settings/options

C0068

*

Operating status

VH

Bit

Assignment

3|2|1|0

TRIP error number

Submission of the 10th digit of the LECOM error number.
Example: TRIP OH (LECOM no. 50) = 0110 (5)

7|6|5|4

Last communication error

0000 No error

0001 Checksum error

0010 Protocol frame error

0011 Reserved

0100 Invalid code number

0101 Invalid variable value

0110 No access authorisation

0111 Telegram processing interrupted by

new telegram

1111 General error

8

0
1

Controller inhibit (DCTRL1−CINH)
Controller inhibited
Controller enabled

9

0
1

Q

min

threshold reached (PCTRL1−QMIN)

Not reached
Reached

10

0
1

Direction of rotation (NSET1/CW/CCW)
CW rotation
CCW rotation

11

0
1

Pulse inhibit (DCTRL1−IMP)
Power outputs inhibited
Power outputs enabled

12

0
1

Quick stop (DCTRL1−QSP)
Not active
Active

13

0
1

I

max

limit reached (MCTRL1−IMAX)

(C0014 = −5−: torque setpoint)
Not reached
Reached

14

0
1

Frequency setpoint reached
(MCTRL1−RFG1=NOUT)
Wrong
True

15

0
1

TRIP error message (DCTRL1−TRIP)
Not active
Active

C0248

*

LECOM input
selection

VD

0

0000 ... 0255

·

For compatibility with LECOM−A/B drivers V1.0 which do not
support the direct addressing of subcodes (array parameters).

·

C0248 determines the subcode (array element) which is accessed.

·

The attempt to access codes without subcodes with C0248 > 0,
causes an error since the address does not exist.

·

LECOM-A/B drivers from V2.0 on support the direct addressing of
subcodes. Do not use C0248 together with these drivers!

·

With every switch−on, C0248 is set to 0.