3 rated data at a mains voltage of 400/500 v, 1 operation with rated power (normal operation), Rated data at a mains voltage of 400/500 v – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 22: Operation with rated power (normal operation), Technical data
![background image](/manuals/566255/22/background.png)
Technical data
Rated data at 400/500 V mains voltage
3−7
L
EDB82MV752 EN 5.2
3.3
Rated data at a mains voltage of 400/500 V
3.3.1
Operation with rated power (normal operation)
Typical motor power
Three−phase asynchronous motor
(4−pole)
P
N
[kW]
0.55
0.75
1.5
2.2
P
N
[hp]
0.75
1.0
2.0
3.0
8200 motec
Type
E82MV551_4B
E82MV751_4B
E82MV152_4B
E82MV222_4B
Mains voltage
U
mains
[V]
3/PE AC 320 V − 0 % ... 550 V + 0 % ;
45 Hz − 0 % ... 65Hz + 0 %
Data for operation on 3/PE AC
400 V
500 V
400 V
500 V
400 V
500 V
400 V
500 V
Rated mains current
I
mains
[A]
1.8
1.4
2.4
1.9
3.8
3.0
5.5
4.5
Rated output current at
switching frequency
2 kHz
I
N24
[A]
2)
2.1
1.8
2.9
2.4
4.6
3.9
6.7
5.6
4 kHz
8 kHz
I
N8
[A]
1.8
1.6
2.4
2.1
3.9
3.5
5.6
5.0
16 kHz
I
N16
[A]
1.2
1.1
1.6
1.4
2.5
2.3
3.6
3.2
Max. permissible output
current for 60 s at
switching frequency
1)
2 kHz
I
max24
[A]
2.7
2.4
3.6
3.2
5.8
5.2
8.4
7.6
4 kHz
8 kHz
I
max8
[A]
2.7
2.4
3.6
3.2
5.8
5.2
8.4
7.6
16 kHz
I
max16
[A]
1.8
1.6
2.4
2.1
3.9
3.5
5.3
4.8
Output voltage
U
M
[V]
3~ 0 ... U
mains
/ 0 ... 650 Hz
Power loss (operation with I
N8
)
P
v
[W]
35
45
70
95
Dimensions
L x W x H [mm]
202 x 156 x 151
230 x 176 x 167
Weight
m [kg]
2.8
2.8
4.1
4.1
Typical motor power
Three−phase asynchronous motor
(4−pole)
P
N
[kW]
3.0
4.0
5.5
7.5
P
N
[hp]
4.1
5.4
7.5
10.2
8200 motec
Type
E82MV302_4B
E82MV402_4B
E82MV552_4B
E82MV752_4B
Mains voltage
U
mains
[V]
3/PE AC 320 V − 0 % ... 550 V + 0 % ;
45 Hz − 0 % ... 65Hz + 0 %
Data for operation on 3/PE AC
400 V
500 V
400 V
500 V
400 V
500 V
400 V
500 V
Rated mains current
I
mains
[A]
9.5
7.6
12.3
9.8
16.8
13.4
21.5
17.2
Rated output current at
switching frequency
2 kHz
I
N24
[A]
2)
8.8
7.0
11.4
9.2
15.6
12.5
16.5
13.2
4 kHz
8 kHz
I
N8
[A]
7.3
5.8
9.5
7.6
13.0
10.4
16.5
13.2
16 kHz
I
N16
[A]
4.7
4.2
6.1
5.5
8.4
7.6
10.7
9.6
Max. permissible output
current for 60 s at
switching frequency
1)
2 kHz
I
max24
[A]
11.0
8.7
14.2
11.4
19.5
15.6
24.8
19.8
4 kHz
8 kHz
I
max8
[A]
11.0
8.7
14.2
11.4
19.5
15.6
24.8
19.8
16 kHz
I
max16
[A]
7.1
6.4
9.1
8.2
12.7
11.4
16.1
14.5
Output voltage
U
M
[V]
3~ 0 ... U
mains
/ 0 ... 650 Hz
Power loss (operation with I
N8
)
P
v
[W]
14o
180
230
290
Dimensions
L x W x H [mm]
325 x 211 x 163 (223**)
Weight
m [kg]
9.7
9.7
9.7
9.7
Bold print = data for operation at a switching frequency of 8 kHz (Lenze setting)
1)
Currents for periodic load change: 1 min overcurrent time with I
max
and 2 min base load time with 75 % I
Nx
2)
Under different operating conditions possible for some types: Operation with increases rated output current with the same load change
cycle (
**