Function library
Configuration of analog and digital setpoints and actual values
7−43
L
EDB82MV752 EN 5.2
7.6.5
Setpoints via fixed setpoints (JOG)
Description
You can store up to three fixed setpoints per parameter set and retrieve them using digital input
signals.
At operation with application I/O 7 fixed setpoints are available per parameter set.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0037
JOG1
20.00
−650.00
{0.02 Hz}
650.00 JOG = fixed setpoint
Additional fixed setpoints
ð C0440
^ 7−43
C0038
JOG2
30.00
−650.00
{0.02 Hz}
650.00
C0039
JOG3
40.00
−650.00
{0.02 Hz}
650.00
C0440
(A)
Additional JOG
values
−650.00
{0.02 Hz}
650.00 JOG = fixed setpoint
Activation via configuration in C0410
^ 7−43
1 JOG 1
20.00
C04401/1 and C0037 are the same
2 JOG 2
30.00
C04401/2 and C0038 are the same
3 JOG 3
40.00
C04401/3 and C0039 are the same
4 JOG 4
15.00
5 JOG 5
25.00
6 JOG 6
35.00
7 JOG 7
45.00
Activation
Operation without application I/O
·
The signal NSET1−JOG1/3 must be combined with a digital input signal under C0410/1.
·
The signal NSET1−JOG2/3 must be combined with a digital input signal under C0410/2.
Active setpoint
Level at
NSET1−JOG1/3
NSET1−JOG2/3
other setpoint source
LOW
LOW
JOG 1
HIGH
LOW
JOG 2
LOW
HIGH
JOG 3
HIGH
HIGH
)
Note!
In addition to the free configuration under C0410 you can also use the fixed
assignment under C0007 to combine the function with digital inputs.