Function library

Configuration of analog and digital setpoints and actual values

7−43

L

EDB82MV752 EN 5.2

7.6.5

Setpoints via fixed setpoints (JOG)

Description

You can store up to three fixed setpoints per parameter set and retrieve them using digital input
signals.

At operation with application I/O 7 fixed setpoints are available per parameter set.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0037

JOG1

20.00

−650.00

{0.02 Hz}

650.00 JOG = fixed setpoint

Additional fixed setpoints

ð C0440

^ 7−43

C0038

JOG2

30.00

−650.00

{0.02 Hz}

650.00

C0039

JOG3

40.00

−650.00

{0.02 Hz}

650.00

C0440
(A)

Additional JOG
values

−650.00

{0.02 Hz}

650.00 JOG = fixed setpoint

Activation via configuration in C0410

^ 7−43

1 JOG 1

20.00

C04401/1 and C0037 are the same

2 JOG 2

30.00

C04401/2 and C0038 are the same

3 JOG 3

40.00

C04401/3 and C0039 are the same

4 JOG 4

15.00

5 JOG 5

25.00

6 JOG 6

35.00

7 JOG 7

45.00

Activation

Operation without application I/O

·

The signal NSET1−JOG1/3 must be combined with a digital input signal under C0410/1.

·

The signal NSET1−JOG2/3 must be combined with a digital input signal under C0410/2.

Active setpoint

Level at

NSET1−JOG1/3

NSET1−JOG2/3

other setpoint source

LOW

LOW

JOG 1

HIGH

LOW

JOG 2

LOW

HIGH

JOG 3

HIGH

HIGH

)

Note!

In addition to the free configuration under C0410 you can also use the fixed
assignment under C0007 to combine the function with digital inputs.