9 current-limit controller, Current−limit controller, Function library – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 127: 9 current−limit controller, Process controller, current limitation controller

background image

Function library

Process controller, current limitation controller

7−56

L

EDB82MV752 EN 5.2

7.9

Current−limit controller

Description

For controlling high moments of inertia the current limiting controller (I

max

controller) can be set.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0077*

Gain I

max

controller

0.25

0.00
= P component not
active

{0.01}

16.00

^ 7−56

C0078*

Integral action time
I

max

controller

65

à

130

12

{1 ms}

9990

= I component not

active

à

Only 8200 vector 15 ... 90 kW

^ 7−56

Adjustment

The current limiting controller is factory−set so that the drive is stable.
Setting notes for power control

The current limiting controller must only be adapted in case of a power control with high moments
of inertia:

·

V/f characteristic control (C0014 = 2 or 3)

·

V

P

(C0077):

» 0.06

·

T

i

(C0078):

» 750 ms

)

Note!

C0077 and C0078 are the same for all parameter sets.