13 external fault evaluation, 1 external fault detection, 2 reset of external faults – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 156: External fault detection, Reset of external faults, Function library

background image

Function library

Thermal motor monitoring, error detection

7−85

L

EDB82MV752 EN 5.2

7.13

External fault evaluation

7.13.1

External fault detection

Description

Use the internal digital signal DCTRL1−TRIP−SET to evaluate external disturbances and integrate
them into the monitoring of the system. If an external disturbance is recognised, the controller
indicates the fault EEr and sets controller inhibit.

)

Note!

The function is LOW active.

Activation

·

C0410/11 (DCTRL1−TRIP−SET) must be combined with digital signal source.

·

LOW level at the signal source for DCTRL1−TRIP−SET sets fault message EEr and activates
the controller inhibit.

)

Note!

Use C0007 to carry out a fixed configuration of DCTRL1−TRIP−SET with the digital
inputs X3/E1 ... X3/E4. C0410/11 will be automatically adapted.

7.13.2

Reset of external faults

Description

You can reset a fault message with the internal digital signal DCTRL1−TRIP−RESET, when the cause
of disturbance has been removed.

)

Note!

A LOW−HIGH signal resets the fault message.

Activation

·

C0410/12 (DCTRL1−TRIP−RESET) must be combined with digital signal source.

·

LOW−HIGH signal at the signal source for DCTRL1−TRIP−RESET resets the fault message.

)

Note!

Further options to reset fault messages:

(