Function library

Free connection of digital signals, message output

7−77

L

EDB82MV752 EN 5.2

Examples

·

C0415/2

ð

15: The status message "CCW rotation" is the signal source for X3/A1

·

C0415/1

ð

60: The status of bit 1 of the process data word CAN−IN1/word is the signal

source for K1

)

Note!

The process data input words CAN−IN1.W1/FIF−IN.W1, CAN−IN1.W2/FIF−IN.W2,
CAN−IN2.W1 and CAN−IN2.W2 can be defined as analog word or digital word (16
bit). If you link digital outputs (C0415/x = 60 ... 135), they must be defined as digital
input words. Otherwise the output signal would be incorrect.

Signal level for V−belt monitoring

Please consider the way the signals are mapped with the current threshold C0156 when monitoring
a V−belt (monitoring signals 20, 21, 22):

·

The display value (C0054) is smoothened with a ring memory with 500 ms.

·

The value set under C0156 corresponds to a percentage of the rated controller current I

r

.

·

If you use the control mode V/f characteristic control with square characteristic" (C0014 = 3)
C0156 will be internally adapted via the output frequency:

C0156

int

[%]

+ C0156 [%] @

f

2

[Hz

2

]

C0011

2

[Hz

2

]