Function library, Free connection of analog signals – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 131
Function library
Free connection of analog signals
7−60
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0419
v
(cont.)
Possible analog signals for C0419
Selection 9 ... 25 correspond to the digital
functions of the relay output K1 or the
digital switching output K1
(C0008) or the
digital output A1 (C0117):
LOW = 0 V/0 mA/4 mA/ 0 kHz
HIGH = 10 V/20 mA/10 kHz
^ 7−59
9
Ready for operation (DCTRL1−RDY)
10
TRIP error message (DCTRL1−TRIP)
11
Motor is running (DCTRL1−RUN)
12
Motor is running / CW rotation (DCTRL1−RUN−CW)
13
Motor is running / CCW rotation
(DCTRL1−RUN−CCW)
14
Output frequency = 0 (DCTRL1−NOUT=0)
15
Frequency setpoint reached
(DCTRL1−RFG1=NOUT)
16
Values have fallen below frequency threshold
Q
min
(f < C0017) (PCTRL1−QMIN)
LOW active
17
I
max
limit reached (MCTRL1−IMAX)
C0014 = −5−: Torque setpoint reached
18
Overtemperature (
J
max
− 5 °C)
(DCTRL1-OH-WARN)
19
TRIP or Q
min
or pulse inhibit (IMP) active
(DCTRL1−TRIP−QMIN−IMP)
20
PTC warning (DCTRL1−PTC−WARN)
21
Apparent motor current < current threshold V−belt monitoring min = C0017 22 Apparent motor current < current threshold and min (DCTRL1−(IMOT 23 Apparent motor current < current threshold and 24 Motor phase failure warning (DCTRL1−LP1−WARN) 25 Minimum output frequency reached (f £ C0010) (PCTRL1−NMIN) LOW active
(DCTRL1−IMOT
Apparent motor current = C0054
Current threshold = C0156
Frequency threshold Q
output frequency > Frequency threshold Q
ramp function generator 1: input = output
(DCTRL1−(IMOT