Commissioning
Parameter setting using the keypad
5−3
L
EDB82MV752 EN 5.2
5.2.2
Changing and saving parameters
)
Note!
l
The user menu user is active after mains switching. Change to the menu all to
address all codes.
l
In the different parameter sets only parameter values can be changed with the
keypad.
l
Digital signals must be used to activate a parameter set for operation
(configuration with C0410)!
l
In the function
g the display shows the parameter set which is just active
during operation.
Step
Keys
Result
Action
1.
Connect keypad
g
xx.xx
Hz
Function
g
is activated. The first code in the user menu will be
displayed (C0517/1, Lenze setting: C0050 = output frequency).
2.
If necessary change to
the menu "ALL"
t
Change to function bar 2
3.
wx
o
4.
yz
all
Select menu "ALL" (list of all codes)
5.
t
Confirm selection and change to function bar 1
6.
Select parameter set for
change
t
Change to function bar 2
7.
wx
m
8.
yz
1 ... 4
Select parameter set to be changed
9.
t
Confirm selection and change to function bar 1
10.
Inhibit controller
s
dc
Only necessary if you want to change C0002, C0148, C0174 and/or
C0469
11.
Set parameters
wx
f
12.
yz
XXXX
Select code
13.
x
k
001
For codes without subcodes: Jump automatically to
i
14.
yz
XXX
Select subcode
15.
x
i
16.
yz
XXXXX
Set parameters
17.
v
STOre
Confirm entry if
p
is blinking
w
Confirm entry if
p
is not blinking;
v
is not active
18.
Restart the "loop" at 11. or 6. to set other parameters.