Commissioning

Parameter setting using the keypad

5−3

L

EDB82MV752 EN 5.2

5.2.2

Changing and saving parameters

)

Note!

l

The user menu user is active after mains switching. Change to the menu all to
address all codes.

l

In the different parameter sets only parameter values can be changed with the
keypad.

l

Digital signals must be used to activate a parameter set for operation
(configuration with C0410)!

l

In the function

g the display shows the parameter set which is just active

during operation.

Step

Keys

Result

Action

1.

Connect keypad

g
xx.xx

Hz

Function

g

is activated. The first code in the user menu will be

displayed (C0517/1, Lenze setting: C0050 = output frequency).

2.

If necessary change to
the menu "ALL"

t



Change to function bar 2

3.

wx

o

4.

yz

all

Select menu "ALL" (list of all codes)

5.

t

Œ

Confirm selection and change to function bar 1

6.

Select parameter set for
change

t



Change to function bar 2

7.

wx

m

8.

yz

1 ... 4

Select parameter set to be changed

9.

t

Œ

Confirm selection and change to function bar 1

10.

Inhibit controller

s

dc

Only necessary if you want to change C0002, C0148, C0174 and/or
C0469

11.

Set parameters

wx

f

12.

yz

XXXX

Select code

13.

x

k
001

For codes without subcodes: Jump automatically to

i

14.

yz

XXX

Select subcode

15.

x

i

16.

yz

XXXXX

Set parameters

17.

v

STOre

Confirm entry if

p

is blinking

w

Confirm entry if

p

is not blinking;

v

is not active

18.

Restart the "loop" at 11. or 6. to set other parameters.