Function library – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 74
![background image](/manuals/566255/74/background.png)
Function library
Selection of control mode, optimisation of operating behaviour
7−3
L
EDB82MV752 EN 5.2
Application
Operating mode
Single drives
Setting in C0014
recommended
alternatively
With extremely alternating loads
4
2
With high starting duty
4
2
With speed control (speed feedback)
2
4
With high dynamic response (e. g. positioning and infeed drives)
2
−
With torque setpoint
5
−
With torque limitation (power control)
2
4
Three−phase AC reluctance motors
2
−
Three−phase sliding rotor motors
2
−
Three phase motors with assigned frequency−voltage characteristic
2
−
Pump and fan drives with square−law load characteristic
3
2 or 4
Group drives
(several motors connected to one controller)
Identical motors and identical loads
2
−
Different motors and/or changing loads
2
−
C0014 = 2: linear V/f characteristic control
C0014 = 3: square−law V/F characteristic control
C0014 = 4: vector control
C0014 = 5: sensorless torque control
)
Note!
l
Only change between the operating modes if the controller is inhibited!
l
Do not use the operating mode "Torque control" for applications with power
control!
l
Optimum drive behaviour in process controller applications, e.g. with speed
control or dancer position control can be achieved with the control modes "linear
V/f characteristic control" or with "vector control".
– If you need a high torque at low speed we recommend the operating mode
vector control".