Configuration of analog and digital setpoints and actual values

7−38

L

EDB82MV752 EN 5.2

Example: Calibration when using a process controller

Example for pressure control

If, for instance, the control range of a pressure control is to be limited to a value lower than the rated
sensor value P

r

, the effective pressure setpoint can be proportionally reduced through the gain of

the analog input (C0027, C0414):

·

Actual pressure value via pressure sensor (P

r

= 0 − 200 mbar) at X3/2U (C0412/5 = 4).

·

Analog pressure setpoint via X3/1U (C0412/4 = 1).

·

The maximum pressure is to be limited to 120 mbar. Reduce the effective pressure setpoint via
the gain of the analog input:

C0414

ń1 +

P

1

P

N

@ 100 % + 120 mbar

200 mbar

@ 100 % + 60 %

Gain calculation

Gain [%]

+

f (P

2

)

* f (P

1

)

U (P

2

)

* U (P

1

)

@ 100 % + * 30 % * 100 %

100 %

* 20 % @

100%

+ * 162.5 %

Offset calculation

Offset (P

2

) [%]

+

f (P

2

) [%]

Verstärkung [%]

@ 100 % * U (P

2

) [%]

+ * 30 %

* 162.5 % @

100 %

* 100 % + * 81.5 %

Example: Calibration when using a process controller

Example for pressure control

The control range of a pressure control is to be limited to a value lower than the rated sensor value
P

N

. For this purpose, the effective pressure setpoint can be proportionally reduced through the gain

of the analog input (C0027, C0414):

·

Actual pressure value via pressure sensor (P

N

= 0 − 200 mbar) at X3/2U (C0412/5 = 4).

·

Analog pressure setpoint via X3/1U (C0412/4 = 1).

·

The maximum pressure is to be limited to 120 mbar. Reduce the effective pressure setpoint via
the gain of the analog input.

C0414

ń1 +

P

1

P

N

@ 100 % + 120 mbar

200 mbar

@ 100 % + 60 %