1 technical data, Technical data, General data/operating conditions – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 64: Parameter setting, With communication module lecom−a (rs232)
![background image](/manuals/566255/64/background.png)
Parameter setting
With communication module LECOM−A (RS232)
6−9
L
EDB82MV752 EN 5.2
6.3
Parameter setting using the LECOM−A (RS232) communication
module
The LECOM−A (RS232) communication module connects the controller to a host (e.g. PC) via the
RS232 interface.
You need the following accessory components to use the communication module:
·
Parameterisation software Global Drive Control easy (GDC easy)"
·
PC system cable
·
Connecting cable
6.3.1
Technical data
6.3.1.1
General data/operating conditions
Communication module type
E82ZBL
Communication medium
RS232 (LECOM−A)
Communication protocol
LECOM−A/B V2.0
Character format
7E1: 7 bits ASCII, 1 stop bit, 1 start bit, 1 parity bit (even)
Baud rate [Bit/s]
1200, 2400, 4800, 9600, 19200
LECOM−A node
Slave
Network topology
Point−to−point
Max. number of nodes
1
Max. cable length
15 m
Communication time
See table
PC connection
9−pole Sub−D socket
DC voltage supply
Internal
Insulation voltage to reference
earth/PE
50 V AC
Type of protection
EN60529
IP20
outside the wire range of the terminals
on the motor side
NEMA 250
Protection against accidental contact to
type 1
Climatic conditions
Permissible
Temperature ranges
Storage
IEC/EN 60721−3−1
1K3 (−25 °C...+60 °C)
Transport
IEC/EN 60721−3−2
2K3 (−25 °C...+70 °C)
Operation
IEC/EN 60721−3−3
3K3 (0 °C...+55 °C)
Dimensions (L x B x H)
75 mm x 62 mm x 23 mm