beautypg.com

2 free configuration of analog outputs, Free configuration of analog outputs, Function library – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 130: Free connection of analog signals

background image

Function library

Free connection of analog signals

7−59

L

EDB82MV752 EN 5.2

7.10.2

Free configuration of analog outputs

Description

·

The analog outputs (X3/62, X3/63) and the frequency output (X3/A4) can be freely assigned to
internal analog process signals or monitoring signals. The controller outputs a voltage
proportional to the internal signal at the analog outputs.

·

Currents can also be output when using the application I/O.
– Range: 0 ... 20 mA, as of software version 1.1 also 4 ... 20 mA

– Setting via jumper at module and C0424

·

A signal source can be assigned to several targets.

)

Note!

Use C0111 to permanently assign the analog output X3/62 to some internal signal
sources. C0419/1 is automatically adapted.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0419

v

Free configuration
of analog outputs

Output of analog signals to terminal

^ 7−59

1 X3/62 (AOUT1−IN)

0

Output frequency (MCTRL1−NOUT+SLIP)

A selection in C0111 is copied into
C0419/1. Change of C0419/1 sets
C0111 = 255!

2 (A) X3/63 (AOUT2−IN)

2

Apparent motor current (MCTRL1−IMOT)

3 (A) X3/A4 (DFOUT1−IN)

3

DC−bus voltage (MCTRL1−DCVOLT)

Frequency output: 50 Hz ... 10 kHz

C0419

v

(cont.)

Possible analog signals for C0419

^ 7−59

0

Output frequency (MCTRL1−NOUT+SLIP)

6 V/12 mA/5.85 kHz

º C0011

1

Device utilisation (MCTRL1−MOUT) at V/f
characteristic control (C0014 = 2 or 3)

3 V/6 mA/2.925 kHz

º Rated active inverter

current (active current/C0091)

Actual motor torque (MCTRL1−MACT) with vector
control (C0014 = 4) or sensorless torque control
(C0014 = 5)

3 V/6 mA/2.925 kHz

º rated motor torque

2

Apparent motor current (MCTRL1−IMOT)

3 V/6 mA/2.925 kHz

º rated inverter

current

3

DC−bus voltage (MCTRL1−DCVOLT)

6 V/12 mA/5.85 kHz

º DC 1000 V (400 V

mains)
6 V/12 mA/5.85 kHz

º DC 380 V (230 V

mains)

4

Motor power (MCTRL1−PMOT)

3 V/6 mA/2.925 kHz

º rated motor power

5

Motor voltage (MCTRL1−VOLT)

4.8 V/9.6 mA/4.68 kHz

ºrated motor

voltage

6

1/output frequency (1/C0050) (MCTRL1−1/NOUT)

2 V/4 mA/1.95 kHz

º 0.5 ´ C0011

7

Output frequency within adjusted limits
(DCTRL1−C0010...C0011)

0 V/0 mA/4 mA/0 kHz

º f = f

min

(C0010)

6 V/12 mA/5.85 kHz

º f = f

max

(C0011)

8

Operation with process controller (C0238 = 0, 1):
Actual process controller value (PCTRL1−ACT)

6 V/12 mA/5.85 kHz

º C0011

Operation without process controller (C0238 =
2):