Free configuration of analog outputs
Description
·
The analog outputs (X3/62, X3/63) and the frequency output (X3/A4) can be freely assigned to
internal analog process signals or monitoring signals. The controller outputs a voltage
proportional to the internal signal at the analog outputs.
·
Currents can also be output when using the application I/O.
– Range: 0 ... 20 mA, as of software version 1.1 also 4 ... 20 mA
– Setting via jumper at module and C0424
·
A signal source can be assigned to several targets.
)
Note!
Use C0111 to permanently assign the analog output X3/62 to some internal signal
sources. C0419/1 is automatically adapted.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0419
v
Free configuration
of analog outputs
Output of analog signals to terminal
^ 7−59
1 X3/62 (AOUT1−IN)
0
Output frequency (MCTRL1−NOUT+SLIP)
A selection in C0111 is copied into
C0419/1. Change of C0419/1 sets
C0111 = 255!
2 (A) X3/63 (AOUT2−IN)
2
Apparent motor current (MCTRL1−IMOT)
3 (A) X3/A4 (DFOUT1−IN)
3
DC−bus voltage (MCTRL1−DCVOLT)
Frequency output: 50 Hz ... 10 kHz
C0419
v
(cont.)
Possible analog signals for C0419
^ 7−59
0
Output frequency (MCTRL1−NOUT+SLIP)
6 V/12 mA/5.85 kHz
º C0011
1
Device utilisation (MCTRL1−MOUT) at V/f
characteristic control (C0014 = 2 or 3)
3 V/6 mA/2.925 kHz
º Rated active inverter
current (active current/C0091)
Actual motor torque (MCTRL1−MACT) with vector
control (C0014 = 4) or sensorless torque control
(C0014 = 5)
3 V/6 mA/2.925 kHz
º rated motor torque
2
Apparent motor current (MCTRL1−IMOT)
3 V/6 mA/2.925 kHz
º rated inverter
current
3
DC−bus voltage (MCTRL1−DCVOLT)
6 V/12 mA/5.85 kHz
º DC 1000 V (400 V
mains)
6 V/12 mA/5.85 kHz
º DC 380 V (230 V
mains)
4
Motor power (MCTRL1−PMOT)
3 V/6 mA/2.925 kHz
º rated motor power
5
Motor voltage (MCTRL1−VOLT)
4.8 V/9.6 mA/4.68 kHz
ºrated motor
voltage
6
1/output frequency (1/C0050) (MCTRL1−1/NOUT)
2 V/4 mA/1.95 kHz
º 0.5 ´ C0011
7
Output frequency within adjusted limits
(DCTRL1−C0010...C0011)
0 V/0 mA/4 mA/0 kHz
º f = f
min
(C0010)
6 V/12 mA/5.85 kHz
º f = f
max
(C0011)
8
Operation with process controller (C0238 = 0, 1):
Actual process controller value (PCTRL1−ACT)
6 V/12 mA/5.85 kHz
º C0011
Operation without process controller (C0238 =
2):
Output frequency without slip (MCTRL1−NOUT)