Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 220
Appendix
Code table
14−19
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0101
(A)
Acceleration times
− main setpoint
0.00
{0.02 s}
1300.00
^ 7−24
1 C0012
5.00
Binary coding of the digital signal sources
assigned to C0410/27 and C0410/28
determine the active time pair
2 T
ir
1
2.50
3 T
ir
2
0.50
4 T
ir
3
10.00
C0103
(A)
Deceleration times
− main setpoint
0.00
{0.02 s}
1300.00 C0410/27
C0410/28
LOW
LOW
HIGH
LOW
LOW
HIGH
HIGH
HIGH
Active
C0012; C0013
T
ir
1; T
if
1
T
ir
2; T
if
2
T
ir
3; T
if
3
1 C0013
5.00
2 T
if
1
2.50
3 T
if
2
0.50
4 T
if
3
10.00
C0105
Deceleration time
quick stop (QSP)
5.00
0.00
{0.02 s}
1300.00
·
Quick stop (QSP) decelerates the drive
to standstill according to the ramp set
under C0105.
·
If the output frequency falls below the
threshold C0019, the DC−injection brake
(DCB) will be activated.
·
The S−shaped ramp (C0182) has also an
effect on quick stop!
– Reduce the time setting under C0105
to reach the desired deceleration
time for quick stop.
– The S−shaped ramp for the quick stop
can be switched off under C0311 (as
of software 3.1).
^ 7−27
C0106
Hold time for
automatic
DC−injection brake
(Auto DCB)
0.50
0.00
= auto DCB not active
{0.01 s}
999.00
=
¥
Hold time, if DC−injection brake is activated
because the value falls below the setting
under C0019.
^ 7−30
C0107
Hold time DC
injection brake
(DCB)
999.00 1.00
{0.01 s}
999.00
=
¥
Hold time, if DC−injection brakes are
activated via an external terminal or control
word.
^ 7−30
C0108*
Gain analog output
X3/62
(AOUT1−GAIN)
128
0
{1}
255 Standard I/O: C0108 and C0420 are the
same
Application I/O: C0108 and C0420/1 are the
same
^ 7−59
C0109*
Offset analog
output X3/62
(AOUT1−OFFSET)
0.00
−10.00
{0.01 V}
10.00 Standard I/O: C0109 and C0422 are the
same
Application I/O: C0109 and C0422/1 are the
same
^ 7−59