Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 232
Appendix
Code table
14−31
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0311*
v
Functions for
special applications
2
1
0
Functions are switched off
By entering the sum of the selected values
you can activate a combination of the
functions.
(C0156 as of
software 3.1,
C0056 as of
software 3.5)
1
Selection:
·
Reference value for the current
threshold C0156
·
Display value in C0056
Function is active:
Function is switched off:
In the operating mode V/f characteristic control
In the operating mode V/f characteristic
control:
·
C0156: Rated controller current
·
C0156: Rated controller current
·
C0056: Controller load (MCTRL−MOUT)
·
C0056: Controller load (MCTRL−MOUT)
In the operating mode vector control or
sensorless torque control:
In the operating mode vector control or
sensorless torque control: Rated motor
torque
·
C0156: Rated controller current
·
C0156: Rated motor torque
·
C0056: Controller load (MCTRL−MOUT)
·
C0056: Actual torque value
(MCTRL-MACT)
(As of software
version 3.1)
2
Effect of the S−shaped ramp
Function is active:
Function is switched off:
The S−shaped ramp (C0182) has no effect on the
quick stop ramp (C0105).
The S−shaped ramp (C0182) has also an
effect on quick stop.
(As of software
version 3.5)
4
Selection of the flying restart function
Function is active:
Function is switched off:
Flying restart function optimised for two−pole
motors is active
Standard flying restart function is active
C0320
(A)
Actual process
controller value
(PCTRL1−ACT)
−650.00
{0.02 Hz}
650.00 Only display
C0321
(A)
Process controller
setpoint
(PCTRL1−SET)
−650.00
{0.02 Hz}
650.00 Only display
C0322
(A)
Process controller
output without
precontrol
(PCTRL1−OUT)
−650.00
{0.02 Hz}
650.00 Only display
C0323
(A)
Ramp function
generator input
(NSET1−RFG1−IN)
−650.00
{0.02 Hz}
650.00 Only display
C0324
(A)
Ramp function
generator output
(NSET1−NOUT)
−650.00
{0.02 Hz}
650.00 Only display
C0325
(A)
PID controller
output
(PCTRL1−PID−OUT)
−650.00
{0.02 Hz}
650.00 Only display
C0326
(A)
Process controller
output
(PCTRL1−NOUT)
−650.00
{0.02 Hz}
650.00 Only display
C0350*
v
System bus node
address
1
1
{1}
63
·
Only for the E82ZAFCC system bus
function module on the FIF interface.
·
Changes will become effective after the
command "reset node"
During operation with 217x
communication modules the node
address must be set under C0009.