Appendix

Code table

14−31

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0311*

v

Functions for
special applications
2

1

0

Functions are switched off

By entering the sum of the selected values
you can activate a combination of the
functions.

(C0156 as of
software 3.1,
C0056 as of
software 3.5)

1

Selection:

·

Reference value for the current
threshold C0156

·

Display value in C0056

Function is active:

Function is switched off:

In the operating mode V/f characteristic control

In the operating mode V/f characteristic
control:

·

C0156: Rated controller current

·

C0156: Rated controller current

·

C0056: Controller load (MCTRL−MOUT)

·

C0056: Controller load (MCTRL−MOUT)

In the operating mode vector control or
sensorless torque control:

In the operating mode vector control or
sensorless torque control: Rated motor
torque

·

C0156: Rated controller current

·

C0156: Rated motor torque

·

C0056: Controller load (MCTRL−MOUT)

·

C0056: Actual torque value
(MCTRL-MACT)

(As of software
version 3.1)

2

Effect of the S−shaped ramp

Function is active:

Function is switched off:

The S−shaped ramp (C0182) has no effect on the
quick stop ramp (C0105).

The S−shaped ramp (C0182) has also an
effect on quick stop.

(As of software
version 3.5)

4

Selection of the flying restart function

Function is active:

Function is switched off:

Flying restart function optimised for two−pole
motors is active

Standard flying restart function is active

C0320
(A)

Actual process
controller value
(PCTRL1−ACT)

−650.00

{0.02 Hz}

650.00 Only display

C0321
(A)

Process controller
setpoint
(PCTRL1−SET)

−650.00

{0.02 Hz}

650.00 Only display

C0322
(A)

Process controller
output without
precontrol
(PCTRL1−OUT)

−650.00

{0.02 Hz}

650.00 Only display

C0323
(A)

Ramp function
generator input
(NSET1−RFG1−IN)

−650.00

{0.02 Hz}

650.00 Only display

C0324
(A)

Ramp function
generator output
(NSET1−NOUT)

−650.00

{0.02 Hz}

650.00 Only display

C0325
(A)

PID controller
output
(PCTRL1−PID−OUT)

−650.00

{0.02 Hz}

650.00 Only display

C0326
(A)

Process controller
output
(PCTRL1−NOUT)

−650.00

{0.02 Hz}

650.00 Only display

C0350*

v

System bus node
address

1

1

{1}

63

·

Only for the E82ZAFCC system bus
function module on the FIF interface.

·

Changes will become effective after the
command "reset node"

During operation with 217x
communication modules the node
address must be set under C0009.