Installation, Electrical installation − connections, Signal type and range selection by dip switch – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 35

background image

Installation

Electrical installation − Connections

4−10

L

EDB82MV752 EN 5.2

Supply via the internal voltage source (X3/20):

·

X3/28, controller inhibit (CINH)

·

X3/E1 .... X3/E4, digital inputs

GND1

62

8 9

20 28 E1 E2 E3 E4 39 A1 59

X3

GND1

GND2

+5V

+20V

8 9

7

0…+

5V

1k … 10k

AIN1

AOUT1

DIGOUT1

7

7

E82ZAFS004

Supply via an external voltage source:

·

X3/28, controller inhibit (CINH)

·

X3/E1 ... X3/E4, digital inputs

GND2

8 9

7

0…+

5V

1k … 10k

GND1

62 7 8 9

20 28 E1 E2 E3 E4 39 A1 59

X3

7

GND1

+5V

+20V

+

_

24 V ext.

(+12 V DC - 0 %

...

+30 V DC + 0 %,

max. 120 mA)

AIN1

AOUT1

DIGOUT1

E82ZAFS005

Min. wiring required for operation

Signal type and range selection by DIP switch

1

ON

2 3 4 5

ON

OFF

)

Note!

DIP switch and C0034 must be set for the same value range, otherwise the analog
input signal at X3/8 will be interpreted incorrectly by the basic unit.

If a setpoint potentiometer is internally supplied through X3/9, the DIP switch must
be set for a voltage range of 0 ... 5 V. Otherwise it is not possible to use the whole
speed range.

−3−

Switch position

Signal at X3/8

1

2

3

4

5

C0034

0 ... 5 V

OFF

OFF

ON

OFF

OFF

0

0 ... 10 V (Lenze setting)

OFF

OFF

ON

OFF

ON

0

0 ... 20 mA

OFF

OFF

ON

ON

OFF

0

4 ... 20 mA

OFF

OFF

ON

ON

OFF

1

4 ... 20 mA

Open−circuit monitoring

OFF

OFF

ON

ON

OFF

3

−10 V ... +10 V

ON

ON

OFF

OFF

OFF

2