Function library

Free connection of analog signals

7−57

L

EDB82MV752 EN 5.2

7.10

Free interconnection of analog signals

7.10.1

Free configuration of analog input signals

Description

·

Internal analog signals can be freely assigned to external analog signal sources:
– Analog inputs (X3/8, X3/1U, X3/2U, X3/1I, X3/2I)
– Frequency input
– Function Motor potentiometer"
– Analog process data input words

·

A signal source can be assigned to several targets.

)

Note!

Use C0005 to configure some of the signal sources for analog inputs. The
corresponding subcodes of C0412 will be adapted automatically.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0412

v

Free configuration
of analog input
signals

Link between analog signal sources and internal analog
signals

A selection under C0005 or C0007 will
be copied to the corresponding subcode
of C0412. A change of C0412 sets C0005
= 255, C0007 = 255!

^ 7−57

1 Setpoint 1

(NSET1–N1)

1

Analog input 1 (AIN1−OUT):
X3/8 (Standard−I/O)
X3/1U or X3/1I (Application−I/O)

Either NSET1−N1 or
NSET1−N2 active
Changeover with C0410/17

Parameter
channel:
C0046

2 Setpoint 2

(NSET1−N2)

1

Parameter
channel:
C0044

3 Additional setpoint

(PCTRL1−NADD)

255

Not assigned (FIXED−FREE) or selected via keypad
or parameter channel of an AIF bus module

Is added to NSET1−N1,
NSET1−N2, JOG values and
the function

j

of the

keypad

Parameter
channel:
C0049

4 Process controller

setpoint 1
(PCTRL1−SET1)

255

Not assigned (FIXED−FREE) or selected via keypad
or parameter channel of an AIF bus module

5 Act. process

controller value
(PCTRL1−ACT)

255

Not assigned (FIXED−FREE) or selected via keypad
or parameter channel of an AIF bus module

Parameter
channel:
C0051, if
C0238 = 1, 2

6 Torque setpoint or

torque limit value
(MCTRL1−MSET)

255

Not assigned (FIXED−FREE) or selected via keypad
or parameter channel of an AIF bus module

·

Observe C0014!

·

Actual torque values
not required.

·

16384

º 100 % torque

setpoint

·

Condition for selection
via terminal (C0412/6 =
1, 2 or 4):

– The gain of the

analog input is set
to: C0414/x, C0426
= 32768/C0011 [%]

Parameter
channel:
C0047

7 Reserved

255

Not assigned (FIXED−FREE) or selected via keypad
or parameter channel of an AIF bus module

8 MCTRL1−VOLT−ADD

255

Not assigned (FIXED−FREE) or selected via keypad
or parameter channel of an AIF bus module

Only for special applications. Modifications
only when agreed on by Lenze!

9 MCTRL1−PHI−ADD

255

Not assigned (FIXED−FREE) or selected via keypad
or parameter channel of an AIF bus module