Parameter setting
With keypad
6−6
L
EDB82MV752 EN 5.2
6.2.6
Remote parameterisation of system bus nodes
Tip!
Instead of using the
n
function, the system bus node can also be selected via C0370.
Action
Key
sequence
Result
Comment
Example
1.
Select
function
t
Change to function bar 2
Remote parameterisation of
system bus node 32.
2.
wx n
3.
Select node
address
yz 1 ... 63
Select node address. (
^ )
32
4.
t
r
Confirm address and change to function bar 1
The node can be parameterised remotely now
5.
Set
parameters
As described in chapter 6.2.4
All settings are redirected to the selected node
6.2.7
Change entries in the user menu
Tip!
Detailed information on the user menu:
(
^ 7−95)
Action
Key
sequence
Result
Comment
Example
1.
Change the
"ALL" menu
t
Change to function bar 2
2.
wx o
3.
yz all
Select menu "ALL" (list of all codes)
4.
t
Confirm selection and change to function bar 1
5.
Select user
menu
x
f
Enter C0014 (operating mode)
to position 2 in the user menu.
The existing setting will be
overwritten.
6.
z
0517
Code for user menu
0517
7.
Select
memory
location
wx K
001
Code saved in C0517/1 is displayed
(Lenze setting: output frequency C0050)
8.
z
001 ... 010
Select subcode
002
9.
Change entry
x
i
10.
yz XXXXX
Enter code number
It is not checked whether the code number exists!
Enter
"0"
to delete the entry.
14
11.
v STOre
Confirm entry
12.
Restart "loop" at 7. again, in order to change further memory locations