Function library, Free connection of digital signals, message output – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 142
![background image](/manuals/566255/142/background.png)
Function library
Free connection of digital signals, message output
7−71
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0410
v
(cont.)
Digital signal sources for C0410
^ 7−68
0
Not assigned (FIXED−FREE)
1
Digital input X3/E1 (DIGIN1)
2
Digital input X3/E2 (DIGIN2)
3
Digital input X3/E3 (DIGIN3)
4
Digital input X3/E4 (DIGIN4)
5 (A)
Digital input X3/E5 (DIGIN5)
6 (A)
Digital input X3/E6 (DIGIN6)
7
PTC input (X2.2/T1, X2.2/T2)
T1/T2 can only be connected to
potential−free switches!
T1/T2 is active ("HIGH") when the switch is
closed
AIF control word (AIF−CTRL)
10
Bit 0
...
...
25
Bit 15
CAN−IN1.W1 or FIF−IN.W1
30
Bit 0
...
...
45
Bit 15
CAN−IN1.W2 or FIF−IN.W2
50
Bit 0
...
...
65
Bit 15
CAN−IN2.W1
70
Bit 0
...
...
85
Bit 15
CAN−IN2.W2
90
Bit 0
...
...
105
Bit 15
Status application I/O
Only active when using application I/O
140
Torque threshold 1 reached (MSET1=MOUT)
141
Torque threshold 2 reached (MSET2=MOUT)
142
Process controller output limit reached
(PCTRL1−LIM)
143...172 Reserved
200
Control words are assigned bit by bit from the
fieldbus function module to FIF (e.g. INTERBUS or
PROFIBUS−DP)
See C0005
Digital output signals
201
as C0415, selection 1
...
...
231
as C0415, selection 31
255
Not assigned (FIXED−FREE)