Function library

Selection of control mode, optimisation of operating behaviour

7−17

L

EDB82MV752 EN 5.2

7.2.4

Skip frequencies

Description

With certain output frequencies, mechanical resonances might occur (e. g. fan).The skip frequencies
suppress these unwanted output frequencies. The bandwidth (

nf) determines the skip frequency

range.

The function is in the block NSET1 before the ramp function generator.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0625*

Skip frequency 1

0.00

0.00

{0.02 Hz}

650.00

^ 7−17

C0626*

Skip frequency 2

0.00

0.00

{0.02 Hz}

650.00

C0627*

Skip frequency 3

0.00

0.00

{0.02 Hz}

650.00

C0628*

Bandwidth of skip
frequencies

0.00

0.00

{0.01 %}

100.00 Applies to C0625, C0626, C0627

Adjustment

)

Note!

l

Skip frequencies only effect main setpoints.

l

C0625, C0626, C0627, C0628 are the same for all parameter sets.

·

Set the required skip frequencies under C0625, C0626, C0627.

·

C0628 defines the bandwidth for skip frequencies.
– Calculation of bandwidth (

Ff) for the respective skip frequency:

Df [Hz] + 2 @ f

s

[Hz]

@

C0628 [%]

100 %

f

s

Skip frequency

C0627

C0626

C0625

f

in

f

out

-

f = 2 x C0625 x C0628

100 %

-

f = 2 x C0626 x C0628

100 %

-

f = 2 x C0627 x C0628

100 %

8200vec525

Fig. 7−4

Effect of the skip frequencies

f

in

Input frequency of the function

f

out

Output frequency of the function