Function library
Selection of control mode, optimisation of operating behaviour
7−17
L
EDB82MV752 EN 5.2
7.2.4
Skip frequencies
Description
With certain output frequencies, mechanical resonances might occur (e. g. fan).The skip frequencies
suppress these unwanted output frequencies. The bandwidth (
nf) determines the skip frequency
range.
The function is in the block NSET1 before the ramp function generator.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0625*
Skip frequency 1
0.00
0.00
{0.02 Hz}
650.00
^ 7−17
C0626*
Skip frequency 2
0.00
0.00
{0.02 Hz}
650.00
C0627*
Skip frequency 3
0.00
0.00
{0.02 Hz}
650.00
C0628*
Bandwidth of skip
frequencies
0.00
0.00
{0.01 %}
100.00 Applies to C0625, C0626, C0627
Adjustment
)
Note!
l
Skip frequencies only effect main setpoints.
l
C0625, C0626, C0627, C0628 are the same for all parameter sets.
·
Set the required skip frequencies under C0625, C0626, C0627.
·
C0628 defines the bandwidth for skip frequencies.
– Calculation of bandwidth (
Ff) for the respective skip frequency:
Df [Hz] + 2 @ f
s
[Hz]
@
C0628 [%]
100 %
f
s
Skip frequency
C0627
C0626
C0625
f
in
f
out
-
f = 2 x C0625 x C0628
100 %
-
f = 2 x C0626 x C0628
100 %
-
f = 2 x C0627 x C0628
100 %
8200vec525
Fig. 7−4
Effect of the skip frequencies
f
in
Input frequency of the function
f
out
Output frequency of the function