Function library, Free connection of analog signals – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 132
Function library
Free connection of analog signals
7−61
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0419
v
(cont.)
Possible analog signals for C0419
^ 7−59
26
Output frequency normalised without slip
(MCTRL1−NOUT−NORM)
27
Output frequency without slip (MCTRL1−NOUT)
6 V/12 mA/5.85 kHz
º C0011
28
Actual process controller value (PCTRL1−ACT)
29
Process controller setpoint (PCTRL1−SET1)
6 V/12 mA/5.85 kHz
º C0011
30
Process controller output without feedforward
control (PCTRL1−OUT)
31
Ramp function generator input (NSET1−RFG1−IN)
32
Ramp function generator output (NSET1−NOUT)
33 (A)
PID controller output (PCTRL1−PID−OUT)
34 (A)
Process controller output (PCTRL1−NOUT)
35
Input signal at X3/8 (standard I/O) or X3/1U or
X3/1I (application I/O), assessed with gain
(C0414/1 or C0027) and offset (C0413/1 or
C0026) (AIN1−OUT)
6 V/12 mA/5.85 kHz
º maximum value of
analog input signal (5 V, 10 V, 20 mA,
10 kHz)
Condition: The gain of the analog input or
frequency input is set to:
C0414/x, C0426 = 100 %
36
Input signal at frequency input X3/E1 and X3/E2,
assessed with gain (C0426) and offset (C0427)
(DFIN1−OUT)
37
Motor potentiometer output
×(MPOT1−OUT)
38 (A)
Input signal at X3/2U or X3/2I, assessed with gain
(C0414/2) and offset (C0413/2) (AIN2−OUT)
40
AIF input word 1 (AIF−IN.W1)
Setpoints to the controller from
communication module on AIF
10 V/20 mA/10 kHz
º 1000
41
AIF input word 2 (AIF−IN.W2)
50
CAN−IN1.W1 or FIF−IN.W1
Setpoints to controller from function module
on FIF
10 V/20 mA/10 kHz
º 1000
51
CAN−IN1.W2 or FIF−IN.W2
52
CAN−IN1.W3 or FIF−IN.W3
53
CAN−IN1.W4 or FIF−IN.W4
60
CAN−IN2.W1
61
CAN−IN2.W2
62
CAN−IN2.W3
63
CAN−IN2.W4
255
Not assigned (FIXED−FREE)
C0108*
Gain analog output
X3/62
(AOUT1−GAIN)
128
0
{1}
255 Standard I/O: C0108 and C0420 are the
same
Application I/O: C0108 and C0420/1 are the
same
^ 7−59
C0109*
Offset analog
output X3/62
(AOUT1−OFFSET)
0.00
−10.00
{0.01 V}
10.00 Standard I/O: C0109 and C0422 are the
same
Application I/O: C0109 and C0422/1 are the
same
^ 7−59
C0420*
Gain analog output
X3/62
(AOUT1−GAIN)
Standard I/O
128
0
{1}
255 128
º Gain 1
C0420 and C0108 are the same
^ 7−59
C0422*
Offset analog
output X3/62
(AOUT1−OFFSET)
Standard I/O
0.00
−10.00
{0.01 V}
10.00 C0422 and C0109 are the same
^ 7−59
C0420*
(A)
Gain analog outputs
Application I/O
128
º Gain 1
^ 7−59
1 X3/62
(AOUT1−GAIN)
128
0
{1}
255 C0420/1 and C0108 are the same
2 X3/63
(AOUT2−GAIN)