Motor data entry/automatic detection

7−48

L

EDB82MV752 EN 5.2

7.7

Automatic detection of motor data

Description

This function serves to detect the required motor data and the motor cable influences.

Must be done before the first commissioning of vector control (C0014 = 4) or sensorless torque
control (C0014 = 5). Otherwise commissioning is not possible.

)

Note!

The motor parameter identification influences the smooth running behaviour in the
control mode "V/f characteristic control with constant U

min

boost" (C0014 = 2 or 3).

If you identify the motor parameters for this control mode, you can optimise the
smooth running behaviour for low speeds.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0084

Motor stator
resistance

0.000

0.000

{0.001

W}

64.000

^ 7−48

0.0

0.0

{0.1 m

W}

6500.0 Only 8200 vector 15 ... 90 kW

C0087

Rated motor speed

à

300

{1 rpm}

16000

à

Depending on the controller

^ 7−48

C0088

Rated motor
current

à

0.0

{0.1 A}

650.0

à

Depending on the controller

0.0 ... 2.0 x rated output current of the
controller

^ 7−48

C0089

Rated motor
frequency

50

10

{1 Hz}

960

^ 7−48

C0090

Rated motor
voltage

à

50

{1 V}

500

à

230 V with 230 V controllers,
400 V with 400 V controllers

^ 7−48

C0091

Motor cos

ϕ

а

0.40

{0.1}

1.0

а

Depending on the controller

^ 7−48

C0092

Motor stator
inductance

0.0

0.000

{0.1 mH}

200.0

^ 7−48

0.00

0.00

{0.01 mH}

200.00 Only 8200 vector 15 ... 90 kW

C0148*

s

Motor parameter
identification

0

0

Ready

Only when the motor is cold!
1. Inhibit controller, wait until drive is at

standstill

2. Enter the correct motor data under

C0087, C0088, C0089, C0090, C0091
(see motor nameplate).

3. Set C0148 = 1 by

v

4. Enable controller

The identification

– starts,

c

goes off

– the motor makes a high−pitched tone,

but does not rotate!

– takes approx. 30 s
– is completed when

c

is on again

5. Inhibit controller

^ 7−48

1

Start identification

·

V/f−rated frequency (C0015), slip
compensation (C0021) and motor stator
inductivity (C0092) are calculated and saved.

·

The motor stator resistance (C0084) = total
resistance of motor cable and motor is
measured and saved