Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 226
Appendix
Code table
14−25
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0156*
Current threshold
0
0
{1 %}
150 Programmable current threshold
·
Reference: Rated controller current
·
Signal output configuration under C0008
or C0415
·
The reference values for vector control
and sensorless speed control can be
changed under C0311 (as of software
version 3.1).
C0161*
Active error
Display history buffer contents
·
Keypad: three−digit, alpha numerical
fault detection
·
9371BB keypad: LECOM fault number
^ 8−1
C0162*
Last fault
C0163*
Last but one fault
C0164*
Last but two fault
C0168*
Actual fault
History buffer displays "active error"
·
Keypad: three−digit, alpha numerical
fault detection
·
9371BB keypad: LECOM fault number
^ 8−1
C0170
v
Configuration TRIP
reset
0
0
TRIP reset by mains switching,
s
, LOW–signal
at X3/28, via function module or communication
module
·
TRIP reset via function module or
communication module with C0043,
C0410/12 or C0135 bit 11.
·
Auto TRIP reset after the time set under
C0171.
^ 8−7
1
like 0 and additional auto TRIP reset
2
TRIP reset through mains switching, via function
module or communication module
3
TRIP reset by mains switching
C0171
Delay for auto−TRIP
reset
0.00
0.00
{0.01 sec}
60.00
C0174*
s
Switching threshold
− brake chopper
100
78
{1 %}
110 Only active with 8200 motec 3 ... 7.5 kW
and 8200 vector 0.55 ... 11 kW, version
for 400/500 V mains voltage
·
100 % = switching threshold DC 790 V
·
110 % = brake chopper switched off
·
U
DC
= switching threshold in V DC
·
The recommended setting considers
max. 10 % mains overvoltage
^ 11−1
Required setting
U
mains
[3/PE AC xxx V]
380
400
415
440
460
480
500
C0174
[%]
78
81
84
89
93
97
100
U
DC
[V DC]
618
642
665
704
735
767
790
C0178*
Operating time
{h}
Only display
Total duration terminal 28 (CINH) = HIGH
C0179*
Power−on time
{h}
Only display
Total time mains on
C0181*
Process controller
setpoint 2
(PCTRL1−SET2)
0.00
−650.00
{0.02 Hz}
650.00
^ 7−53
C0182*
Integration time
S–ramps
0.00
0.00
{0.01 s}
50.00
·
C0182 = 0.00: Linear ramp function
generator operation
·
C0182 > 0.00: S−shaped ramp function
generator (smooth)
^ 7−24
C0183*
Diagnostics
0
No fault
Only display
102
TRIP active
104
Message "Overvoltage (
OU
)" or "Undervoltage
(
LU
)" active
142
Pulse inhibit
151
Quick stop active
161
DC−injection brake active
250
Warning active
C0184*
Frequency
threshold
PCTRL1−I−OFF
0.0
0.0
{0.1 Hz}
25.0
·
If the output frequency < C0184, the
I component of the process controller
will be switched off
·
0.0 Hz = Function not active
^ 7−53