Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 226

background image

Appendix

Code table

14−25

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0156*

Current threshold

0

0

{1 %}

150 Programmable current threshold

·

Reference: Rated controller current

·

Signal output configuration under C0008
or C0415

·

The reference values for vector control
and sensorless speed control can be
changed under C0311 (as of software
version 3.1).

C0161*

Active error

Display history buffer contents

·

Keypad: three−digit, alpha numerical
fault detection

·

9371BB keypad: LECOM fault number

^ 8−1

C0162*

Last fault

C0163*

Last but one fault

C0164*

Last but two fault

C0168*

Actual fault

History buffer displays "active error"

·

Keypad: three−digit, alpha numerical
fault detection

·

9371BB keypad: LECOM fault number

^ 8−1

C0170

v

Configuration TRIP
reset

0

0

TRIP reset by mains switching,

s

, LOW–signal

at X3/28, via function module or communication
module

·

TRIP reset via function module or
communication module with C0043,
C0410/12 or C0135 bit 11.

·

Auto TRIP reset after the time set under
C0171.

^ 8−7

1

like 0 and additional auto TRIP reset

2

TRIP reset through mains switching, via function
module or communication module

3

TRIP reset by mains switching

C0171

Delay for auto−TRIP
reset

0.00

0.00

{0.01 sec}

60.00

C0174*

s

Switching threshold
− brake chopper

100

78

{1 %}

110 Only active with 8200 motec 3 ... 7.5 kW

and 8200 vector 0.55 ... 11 kW, version
for 400/500 V mains voltage

·

100 % = switching threshold DC 790 V

·

110 % = brake chopper switched off

·

U

DC

= switching threshold in V DC

·

The recommended setting considers
max. 10 % mains overvoltage

^ 11−1

Required setting

U

mains

[3/PE AC xxx V]

380
400
415
440
460
480
500

C0174

[%]

78
81
84
89
93
97

100

U

DC

[V DC]

618
642
665
704
735
767
790

C0178*

Operating time

{h}

Only display
Total duration terminal 28 (CINH) = HIGH

C0179*

Power−on time

{h}

Only display
Total time mains on

C0181*

Process controller
setpoint 2
(PCTRL1−SET2)

0.00

−650.00

{0.02 Hz}

650.00

^ 7−53

C0182*

Integration time
S–ramps

0.00

0.00

{0.01 s}

50.00

·

C0182 = 0.00: Linear ramp function
generator operation

·

C0182 > 0.00: S−shaped ramp function
generator (smooth)

^ 7−24

C0183*

Diagnostics

0

No fault

Only display

102

TRIP active

104

Message "Overvoltage (

OU

)" or "Undervoltage

(

LU

)" active

142

Pulse inhibit

151

Quick stop active

161

DC−injection brake active

250

Warning active

C0184*

Frequency
threshold
PCTRL1−I−OFF

0.0

0.0

{0.1 Hz}

25.0

·

If the output frequency < C0184, the
I component of the process controller
will be switched off

·

0.0 Hz = Function not active

^ 7−53