Function library
Configuration of analog and digital setpoints and actual values
7−44
L
EDB82MV752 EN 5.2
Operation with application I/O
·
The signal NSET1−JOG1/3/5 must be combined with a digital input signal under C0410/1.
·
The signal NSET1−JOG2/3/6/7 must be combined with a digital input signal under C0410/2.
·
The signal NSET1−JOG4/5/6/7 must be combined with a digital input signal under C0410/33.
Active setpoint
Level at
NSET1−JOG1/3/5/7
NSET1−JOG2/3/6/7
NSET1−JOG4/5/6/7
other setpoint source
LOW
LOW
LOW
JOG 1
HIGH
LOW
LOW
JOG 2
LOW
HIGH
LOW
JOG 3
HIGH
HIGH
LOW
JOG 4
LOW
LOW
HIGH
JOG 5
HIGH
LOW
HIGH
JOG 6
LOW
HIGH
HIGH
JOG 7
HIGH
HIGH
HIGH
Influence on other setpoints
·
The maximum output frequency (C0011) also limits the fixed setpoints (JOG).
·
The minimum output frequency (C0010) does not limit the fixed setpoints (JOG).
·
Fixed setpoints (JOG) have priority over the analog setpoint 1 (NSET1−N1) and over the analog
setpoint 2 (NSET1−N2).
·
The additional setpoint (PCTRL1−NADD) is added to the fixed setpoints.
Tip
The display of the parameter can be related to a process variable. (
^ 7−86
)