Function library – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 115

background image

Function library

Configuration of analog and digital setpoints and actual values

7−44

L

EDB82MV752 EN 5.2

Operation with application I/O

·

The signal NSET1−JOG1/3/5 must be combined with a digital input signal under C0410/1.

·

The signal NSET1−JOG2/3/6/7 must be combined with a digital input signal under C0410/2.

·

The signal NSET1−JOG4/5/6/7 must be combined with a digital input signal under C0410/33.

Active setpoint

Level at

NSET1−JOG1/3/5/7

NSET1−JOG2/3/6/7

NSET1−JOG4/5/6/7

other setpoint source

LOW

LOW

LOW

JOG 1

HIGH

LOW

LOW

JOG 2

LOW

HIGH

LOW

JOG 3

HIGH

HIGH

LOW

JOG 4

LOW

LOW

HIGH

JOG 5

HIGH

LOW

HIGH

JOG 6

LOW

HIGH

HIGH

JOG 7

HIGH

HIGH

HIGH

Influence on other setpoints

·

The maximum output frequency (C0011) also limits the fixed setpoints (JOG).

·

The minimum output frequency (C0010) does not limit the fixed setpoints (JOG).

·

Fixed setpoints (JOG) have priority over the analog setpoint 1 (NSET1−N1) and over the analog
setpoint 2 (NSET1−N2).

·

The additional setpoint (PCTRL1−NADD) is added to the fixed setpoints.

Tip

The display of the parameter can be related to a process variable. (

^ 7−86

)