beautypg.com

Function library, Free connection of digital signals, message output – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 146

background image

Function library

Free connection of digital signals, message output

7−75

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0415

v

(cont.)

Possible digital signals for C0415

^ 7−73

20

Apparent motor current < current threshold
(DCTRL1−IMOT

V−belt monitoring
Apparent motor current = C0054
Current threshold = C0156
Frequency threshold Q

min

= C0017

21

Apparent motor current < current threshold and
output frequency > Frequency threshold Q

min

(DCTRL1−(IMOT

22

Apparent motor current < current threshold and
ramp function generator 1: input = output
(DCTRL1−(IMOT

23

Motor phase failure warning (DCTRL1−LP1−WARN) Set C0597 = 2

24

Minimum output frequency reached (f

£ C0010)

(PCTRL1−NMIN)

LOW active

25

TRIP error message (DCTRL1−TRIP)

26

Motor is running (DCTRL1−RUN)

27

Motor is running / CW rotation (DCTRL1−RUN−CW)

28

Motor is running / CCW rotation
(DCTRL1−RUN−CCW)

29

Process controller input = process controller
output (PCTRL1−SET=ACT)

30

Reserved

31

Apparent motor current

>

Current threshold and

ramp function generator 1: input = output
(DCTRL1−(IMOT>ILIM)−RFG−I=0)

Overload monitoring
Apparent motor current = C0054
Current threshold = C0156

32

Digital input X3/E1

digital inputs

33

Digital input X3/E2

34

Digital input X3/E3

35

Digital input X3/E4

36 (A)

Digital input X3/E5

37 (A)

Digital input X3/E6

38

PTC input X2.2/T1, X2.2/T2

Only connect potential−free switches to
T1/T2!
T1/T2 is active ("HIGH") when the switch is
closed